EN 61000-4-2 ESD / 4 kV CD / 8 kV AD; EN 61000-4-3 RF radiated / 10 V/m; EN 61000-4-4 Burst / 2 kV; EN 61000-4-6 RF conducted / 10 V; EN 55011 / Class B
Impact strength
1 J
Vibration resistance
EN 60068-2-6 Fc / 20 g (10...3000 Hz) / 50 frequency cycles, 1 octave/minute, in 3 axes
Shock resistance
EN 60068-2-27 Ea / 100 g 11 ms half-sine; 3 shocks in each direction of the 3 coordinate axes
Continuous shock resistance
EN 60068-2-27 / 40 g 6 ms; 4000 shocks in each direction of the 3 coordinate axes
Rapid temperature change
EN 60068-2-14 Na / TA = -40 °C; TB = 85 °C; t1 = 30 min; t2 = < 10 s; 50 cycles
Salt spray test
EN 60068-2-52 Kb / severity level 5 (4 test cycles)
MTTF
1258 years
Embedded software included
Detection range
Real switching distance Sr
4 ± 10 % mm
Working distance
0...3,24 mm
Increased switching distance
Displays / controls
Indication
Switching state / LED, yellow
Electrical connection
Cable
5 m, PUR, Ø 4 mm; flammability according to ECE R118 Rev.2; 3 x 0.34 mm²
Industrial applications / factory automation; use in machine tools, coolant and lubricant systems
Compressive strength
50 bar / 5 MPa
Note on pressure resistance
active surface
Mechanical data
Mounting type
Flush-mountable
Thread designation
M12 x 1
Materials
1.4404 (stainless steel / 316L); active surface: 1.4404 (stainless steel / 316L); LED window: PEI; mounting nuts: brass, white bronze-coated
Tightening moment
15 Nm
Suitable for chain conveyor
All-metal housing
Outputs
Max. voltage drop switching output DC
2,5 V
Continuous current rating of switching output DC
100 mA
Switching frequency DC
100 Hz
Short-circuit protection
Overload resistant
Product features
Electrical version
PNP
Output function
Normally open contact
Switching distance
4 mm
Housing
Threaded design
Dimensions
M12 x 1 / L = 40 mm
Induktiver Sensor, M12 x 1 / L = 40 mm, Schaltabstand 4 mm bündig einbaubar, Schließer, DC, PNP, 5 m PUR-Kabel, IP 65, IP 66, IP 67, IP 68, IP 69K, 3-Leiter, Umgebungstemperatur -40...85 °C, Schaltfrequenz 100 Hz