EN 61000-4-2 ESD / 4 kV CD / 8 kV AD; EN 61000-4-3 HF radiated / 10 V/m; EN 61000-4-4 Burst / 2 kV; EN 61000-4-5 Surge / 0.5 kV line to line, Ri: 2 Ohm; EN 61000-4-6 HF conducted / 10 V; EN 55011 Emission / Class B
MTTF
3216 years
Detection range
Real switching distance Sr
2 ± 10 % mm
Working distance
0...1,6 mm
Displays / controls
Indication
Switching state / 1 x LED, yellow
Electrical connection
Cable
2 m, PUR; 3 x 0.34 mm²
Electrical data
Operating voltage
10...30 DC V
Electricity consumption
< 15 mA
Protection class
II
Reverse polarity protection
Environmental conditions
Ambient temperature
-20...70 °C
Degree of protection
IP 67
Mechanical data
Mounting type
Flush-mountable
Thread designation
M12 x 1
Materials
stainless steel; active surface: PBT
Outputs
Max. voltage drop switching output DC
2,5 V
Continuous current rating of switching output DC
100 mA
Switching frequency DC
1200 Hz
Short-circuit protection type
timed
Short-circuit protection
Overload resistant
Product features
Electrical version
PNP
Output function
Normally open contact
Switching distance
2 mm
Housing
Threaded design
Dimensions
M12 x 1 / L = 31,5 mm
Induktiver Sensor, M12 x 1 / L = 31,5 mm, Schaltabstand 2 mm bündig einbaubar, Schließer, DC, PNP, 2 m PUR-Kabel, IP 67, 3-Leiter, Umgebungstemperatur -20...70 °C, Schaltfrequenz 1200 Hz