Miniature fuse according to IEC60127-2 Sheet 1; ≤ 2 A; fast
Electrical connection - Plug
Plug connection
1 x M12; coding: C; contacts: 3
Electrical data
Operating voltage
20...250 AC/DC V
Protection class
I
Reverse polarity protected
Environmental conditions
Ambient temperature
-25...70 °C
Degree of protection
IP 67
Field of application
Application
Industrial applications / factory automation
Mechanical data
Mounting type
Flush-mountable
Mounting method
DIN rail mounting; (TH35 (EN 60715))
Materials
PPE modified
Outputs
Max. voltage drop switching output DC
6 V
Max. voltage drop switching output AC
6,5 V
Minimum load current
5 mA
Max. residual current
0,8 mA
Continuous current rating of switching output AC
250; (350 (...50 °C)) mA
Continuous current rating of switching output DC
100 mA
Short-term current rating of switching output
2200; (20 ms / 0,5 Hz) mA
Switching frequency AC
25 Hz
Switching frequency DC
25 Hz
Short-circuit-proof
Overload resistant
Product features
Output function
Normally open contact
Switching distance
50 mm
Housing
rectangular
Dimensions
92 x 80 x 40 mm
Remarks
Remarks
Recommendation: After a short circuit, check the device for safe operation.
Induktiver Sensor, 92 x 80 x 40 mm, Schaltabstand 50 mm bündig einbaubar, Schließer, AC/DC, M12 Steckverbindung, IP 67, 2-Leiter, Umgebungstemperatur -25...70 °C, Schaltfrequenz 25 Hz AC / 25 Hz DC