2,5 (250 V AC) / 1,3 (110 V AC) / 0,8 (24 V DC) mA
Continuous current rating of switching output AC
250; (350 (...50 °C)) mA
Continuous current rating of switching output DC
100 mA
Short-term current rating of switching output
2200; (20 ms / 0,5 Hz) mA
Switching frequency AC
10 Hz
Switching frequency DC
10 Hz
Short-circuit-proof
Overload resistant
Product features
Output function
Normally open contact (NO) / Normally closed contact (NC); (selectable)
Switching distance
40 mm
Housing
rectangular
Dimensions
90 x 60 x 40 mm
Remarks
Remarks
Recommendation: After a short circuit, check the device for safe operation.
Inductive sensor, Rectangular, plastics, AC/DC, Terminals, Sensing range 40 mm [nf] adjustable
Operating voltage: 20...250 V AC/DC
Electrical design: AC/DC
Output function: normally open / closed programmable
Current rating (continuous): 250 AC / 100 DC; 350 AC (...50 °C) mA
Current rating (peak): î: 2.2 A (20 ms / 0.5 Hz) mA
Mounting: non-flush mountable
Sensing range: 40, adjustable mm
Switching frequency: 10 Hz
Connection: terminals up to 2.5 mm²
Housing materials: PPE
Ambient temperature: -25...80 °C
Protection: IP 65
Output status indication: LED yellow
Accessories (to be ordered separately): Mounting accessories