Further information for Ifm Electronic DN4011 - Switched mode power supply 24 DC 80 power output
Approvals / tests
EMC
EN 61000-6-1; EN 61000-6-2; EN 61000-6-3; EN 61000-6-4; EN 61000-3-2 / Class A
Vibration resistance
IEC 60068-2-6 / ±1.6 mm 2...17.8 Hz / 2 g 17.8...500 Hz
Shock resistance
IEC 60068-2-27 / 30 g 6 ms / 20 g 11 ms
MTTF
204 years
Power factor correction PFC
complies
Displays / controls
Indication
DC ok / 1 x LED
Electrical data
AC frequency
47...64 Hz
Nominal voltage AC
< 230 V
Input voltage DC
110...300; (-20 % / +25 %) V
Input voltage range AC
100...240; (-10 % / +10 %) V
DC output voltage
24...28 V
Protection class
I; (IEC 61140)
Over voltage protection
ja; (< 39 DC)
Output voltage
adjustable; output voltage according to SELV, PELV V
Max. output current at min. output voltage
3,3 A
Max. output current at max. output voltage
2,7 A
Max. output current short-term at min. output voltage
3,3 A
Max. output current short-term at max. output voltage
2,7 A
Output power (continuous)
80 W
Output power (temporary)
80 W
Power factor (rated voltage 120 V AC / 60 Hz)
0,61
Power factor (rated voltage 230 V AC / 50 Hz)
0,56
Number of output circuits
1
Max. ripple
50 mV
Inrush current (rated voltage 120 V AC / 60 Hz)
23 A
Inrush current at rated voltage 230 V AC / 50 Hz
45 A
Efficiency (rated voltage 120 V AC / 60 Hz)
88 %
Efficiency (rated voltage 230 V AC / 50 Hz)
89,8 %
External input fuse
≥ B-10 A / ≥ C-6 A
Derating
1,8 (60...70 °C) W/K
Power failure bridging time (nominal voltage 120 V AC / 60 Hz)
30 ms
Power failure bridging time (rated voltage 230 V AC / 50 Hz)
128 ms
Input current (rated voltage 120 V AC / 60 Hz)
1,24 A
Input current (rated voltage 230 V AC / 50 Hz)
0,68 A
Power loss (rated voltage 120 V AC / 60 Hz)
11,1 W
Power loss (rated voltage 230 V AC / 50 Hz)
9,1 W
Reverse voltage withstand
35 V
Inrush current limitation
Environmental conditions
Ambient temperature
-25...70 °C
Note on ambient temperature
Allow for free spaces for convection (see operating instructions)
Storage temperature
-40...85 °C
Maximum permissible relative humidity
95; (IEC 60068-2-30) %
Degree of protection
IP 20; (EN 60529)
Pollution degree
2; (IEC 62103: conductive pollution not permitted)
Field of application
Model
DIN rail housing
Mechanical data
Housing
rectangular
Mounting method
DIN rail mounting; (TH35 (EN 60715))
Dimensions
124 x 40 x 122,5 mm
Materials
housing: sheet steel
Outputs
Overload behaviour
constant output current
Overload resistant
Remarks
Remarks
Series connection of outputs is only valid for identical devices up to max. 150 V DC total voltage
Switched-mode power supply 24 V DC, 80 W power output, Primary switched mode, Output current 3.3 A, regulated, NEC Class II Power Source
Application: regulated power supply for sensors, actuators, evaluation electronics and plcs
Nominal voltage: 115 / 230 AC V
Output voltage: 24...28 DC; adjustable; output voltage to SELV, PELV V
Output current: 3.3 (24 V DC) / 2.7 (28 V DC) A
Nominal frequency: 50 / 60 Hz
Efficiency: 88 (120 V AC; 60 Hz) / 89.8 (230 V AC; 50 Hz) %
Connection: screw terminals
Housing materials: steel sheet
Ambient temperature: -25...70, observe the free space for convection (see operating instructions) °C
Protection: IP 20; to EN 60529
Accessories (to be ordered separately): Mounting accessories