| Approvals / tests |
| EMC | EN 61010 / 2011; EMC 89/336/EEC; EN 61000-6-2 / 2005; EN 61000-6-4 / 2007 |
| MTTF | 152 years |
| Displays / controls |
| Indication | OLED display, 128 x 64 pixels self-illuminating; Switch state / LED, green |
| Electrical connection |
| Double chamber terminal block | 2 x ...2.5 mm²; AWG 14 |
| Electrical data |
| Nominal voltage AC | 110...240 V |
| Nominal voltage DC | 27 V |
| Rated voltage tolerance | < 10 % |
| Rated voltage tolerance 2 | 20...10 % |
| Rated frequency AC | 50...60 Hz |
| Power consumption | 3 W |
| Auxiliary power for sensors DC | 19.6...27.7; (SELV, ≤ 15 mA) V |
| Environmental conditions |
| Ambient temperature | -40...60 °C |
| Storage temperature | -40...85 °C |
| Maximum permissible relative humidity | 80; (40 °C: 50 %) % |
| Degree of protection | IP 50 |
| Degree of protection terminals | IP 20 |
| Pollution degree | 2 |
| Field of application |
| Model | DIN rail housing |
| Application | Pulse evaluation system with µprocessor for frequency; speed; velocity; counts and machine cycles |
| Inputs / Outputs |
| Number of inputs and outputs | Number of analogue outputs: 1; Number of relay outputs: 2 |
| Measurement / adjustment range |
| Adjustable range Hz | 0,1...1000 Hz |
| Adjustment range | 1...60000 Imp/min |
| Mechanical data |
| Mounting method | DIN rail mounting; (TH35 (EN 60715)) |
| Materials | Housing: plastic |
| Outputs |
| Number of relay outputs | 2 |
| Contact rating | 6 A (250 V AC, 30 V DC); B300, R300; (resistive load) |
| Number of analogue outputs | 1 |
| Analog output current | 4...20 mA |
| Max. load | 500; (Min. load: 20 [Ω]) Ω |
| Product features |
| Housing | rectangular |
| Dimensions | 78 x 45 x 124,7 mm |
| Remarks |
| Remarks | The device complies with overvoltage category II |