| Accessories |
| Scope of delivery | Cage clamp terminals: 5 |
| Accuracy / Deviations |
| Hysteresis | 1...100 % of Sp |
| Approvals / tests |
| EMC | EN 61000-6-2; EN 61000-6-3 |
| Electrical safety | EN 61010-1; EN 61010-2-201 |
| MTTF | 190 years |
| Displays / controls |
| Indication | Spannungsversorgung / 1 x LED, grün; Eingangssignal / 1 x LED, gelb; Ausgang / 1 x LED, grün; Freigabesignal / 1 x LED, gelb |
| Electrical connection |
| Cage clamp spring terminals | ...2,5 mm² |
| Electrical data |
| Operating voltage | 110...240 AC / 27 DC; (tolerance: -20 % / +10 % ; DC operation: SELV) V |
| Nominal voltage AC | 110...240 V |
| Nominal voltage DC | 27 V |
| Rated frequency AC | 50...60 Hz |
| Electricity consumption | AC operation: max. 8 A (including maximum AC supply for additional devices) mA |
| Maximum power consumption DC | 4 W |
| Over voltage category | II |
| Auxiliary power for sensors DC | 18.5...30; (SELV, short-circuit proof, ≤ 100 mA) V |
| Environmental conditions |
| Ambient temperature | -25...60 °C |
| Note on ambient temperature | Relay output contact rating: B300 max. 50 °C |
| Storage temperature | -25...70 °C |
| Maximum permissible relative humidity | 80; (40 °C: 50 % non-condensing) % |
| Maximum height above sea level | 2000 m |
| Degree of protection | IP 20; (in mounted condition) |
| Degree of protection terminals | IP 20 |
| Pollution degree | 2 |
| Field of application |
| Model | DIN rail housing |
| Application | Universal evaluation of pulse sequences for setpoint over/underflow; Speed monitoring |
| Inputs |
| Number of digital inputs | 2; (1 x frequency ; 1 x release signal) |
| Input circuitry for digital inputs | PNP; (Type 2 according to IEC 61131-2) |
| Input current high | 6...10 mA |
| Input current Low | 0...5 mA |
| High switching level | 11...30 V |
| Low switching level | 0...5 V |
| Inputs / Outputs |
| Number of inputs and outputs | Number of digital inputs: 2; number of digital outputs: 1; number of relay outputs: 1 |
| Measurement / adjustment range |
| Adjustable range Hz | 0,2...2000 Hz |
| Mechanical data |
| Mounting method | DIN rail mounting; (TH35 (EN 60715)) |
| Materials | housing: PC-GF20 |
| Outputs |
| Number of digital outputs | 1 |
| Number of relay outputs | 1 |
| Circuitry | PNP |
| Output current rating | 0,1 A |
| Minimum load current | 10; (> 12 V) mA |
| Contact rating | 6 A; (max. 240 V AC / 30 V DC see diagram: Contact rating ; B300: 6000 cycles) |
| Switching frequency AC | < 0,1 Hz |
| Switching frequency DC | < 0,1 Hz |
| Short-circuit-proof | |
| Galvanically isolated | |
| Product features |
| Housing | rectangular |
| Dimensions | 93 x 25,4 x 109 mm |
| Remarks |
| Remarks | For installation and operation instructions, please refer to the user manual. |
| Response times |
| Start-up bridging | 0,1...15 s |
| Software / Programming |
| Parameterization options | Adjustment of switching function, switching point, hysteresis, and start-up bypass via potentiometer |
Speed monitor, setting range Hz 0.2...2000 Hz, rated voltage AC 110...240 V, rated voltage DC 27 V, number of digital outputs 1, connection terminals