Further information for ifm Electronic AL1401 IO-Link Master PROFINET IP65
Accessories
Scope of delivery
Closure cap: 1 x M12, stainless steel, E12542
Approvals / tests
EMC
EN 61000-6-2; EN 61000-6-4
Shock resistance
DIN EN 60068-2-27
Vibration resistance
DIN EN 60068-2-64 2009-04; DIN EN 60068-2-6 2008-10
MTTF
60 years
Electrical connection - Ethernet
Plug connection
2 x M12; coding: D; contacts: 4; seal: EPDM
Electrical data
Operating voltage
20...28 DC; (US ; after PELV) V
Electricity consumption
300...3900; (US) mA
Protection class
III
Additional power supply
20...30 DC; (UA) V
Total current rating
8 A
Current rating per port
2; (adjustable: 0...2; factory default: 2) A
Environmental conditions
Ambient temperature
-25...60 °C
Storage temperature
-25...85 °C
Maximum permissible relative humidity
90 %
Degree of protection
IP 65; IP 66; IP 67; IP 69K; (Operation with stainless steel closure caps: IP 69K)
Degree of protection (NEMA 250)
6P
Pollution degree
2
Chemical media
ISO 16750-5 / HLP, CC, DB, DC, DD, CA; NEMA 250 5.13.1 / AA; DIN EN ISO 175, Ecolab test method 40-1; The following media were tested for 28 days at constant room temperature using the stand and immersion test / P3-topax 990; Topactive 200; Topactive 500; Topactive OKTO
Field of application
Application
Hygiene area; I/O modules for field use
Pass-through function
Power supply; Fieldbus interface
Inputs
Number of digital inputs
4; (IO-Link Port Class B: 4 x 1)
High switching level
11...30 V
Low switching level
0...5 V
Short-circuit resistance digital inputs
Inputs / Outputs
Total number of inputs and outputs
12; (configurable)
Number of inputs and outputs
Number of digital inputs: 4; Number of digital outputs: 8
Interfaces
Communication interface
Ethernet; IO-Link
Transmission standard
100Base-TX
Transmission rate
100 MBit/s
Protocol
PROFINET
Factory settings
IP address: 0.0.0.0; Subnet mask: 0.0.0.0; Gateway IP address: 0.0.0.0; MAC address: see nameplate
Note on interfaces
IO-Link Integration Edition 2; CC-C (Conformance Class C) (IRT-Switch); S2-Redundancy; Netload Class III; CiR (Configuration in Run); SNMP (Simple Network Management Protocol); MRP (Media Redundancy Protocol); Supported network topologies: Line; Ring
Housing: PA grey; Socket: 1.4404 (stainless steel / 316L)
Sealing material
EPDM
Outputs
Number of digital outputs
8; (IO-Link Port Class B: 4 x 2)
Current rating per output
2000 mA
Short-circuit-proof
Remarks
Remarks
For further information, please refer to the operating instructions.
IO-Link Master mit PROFINET-Schnittstelle, Ethernet, IO-Link, PROFINET, 152 x 59,3 x 38,4 mm, Anzahl der digitalen Eingänge 4, Anzahl der digitalen Ausgänge 8, Durchschleiffunktion Spannungsversorgung, Feldbusschnittstelle, IP 65, IP 66, IP 67, IP 69K, (Betrieb mit Edelstahl-Verschlusskappen: IP 69K)