| Approvals / tests |
| EMC | EN 61000-6-2; EN 61000-6-4 |
| Shock resistance | DIN EN 60068-2-27 |
| Vibration resistance | DIN EN 60068-2-64 2009-04; DIN EN 60068-2-6 2008-10 |
| MTTF | 78 years |
| Electrical connection - Ethernet |
| Plug connection | 3 x M12; coding: D; contacts: 4; seal: FKM |
| Electrical data |
| Operating voltage | 20...30 DC; (US; according to SELV/PELV) V |
| Electricity consumption | 300...3900; (US) mA |
| Protection class | III |
| Total current rating | 3,6 A |
| Environmental conditions |
| Ambient temperature | -25...60 °C |
| Storage temperature | -25...85 °C |
| Maximum permissible relative humidity | 90 % |
| Degree of protection | IP 65; IP 66; IP 67 |
| Degree of protection (NEMA 250) | 6P |
| Pollution degree | 2 |
| Chemical media | ISO 16750-5 / AA, BA, BD, HLP, CC, DB, DC, DD, CA; NEMA 250 5.13.1 / AA |
| Field of application |
| Application | I/O modules for field use |
| Pass-through function | Fieldbus interface |
| Inputs |
| Number of digital inputs | 16; (IO-Link Port Class A: 8 x 2) |
| High switching level | 11...30 V |
| Low switching level | 0...5 V |
| Short-circuit resistance digital inputs | |
| Inputs / Outputs |
| Total number of inputs and outputs | 16; (configurable) |
| Number of inputs and outputs | Number of digital inputs: 16; Number of digital outputs: 8 |
| Interfaces |
| Communication interface | Ethernet; IO-Link |
| Transmission standard | 100Base-TX |
| Transmission rate | 100 MBit/s |
| Protocol | PROFINET |
| Factory settings | IP address: 0.0.0.0; Subnet mask: 0.0.0.0; Gateway IP address: 0.0.0.0; MAC address: see nameplate |
| Note on interfaces | CC-C (Conformance Class C) (IRT-switch); Netload Class III; SNMP (Simple Network Management Protocol); MRP (Media Redundancy Protocol); supported network topologies: line; ring |
| Transmission type | COM1 (4.8 kBaud); COM2 (38.4 kBaud); COM3 (230.4 kBaud) |
| IO-Link revision | 1.1 |
| Number of Class A ports | 8 |
| Mechanical data |
| Housing | rectangular |
| Mounting method | Rear panel mounting |
| Dimensions | 208 x 59,3 x 38,4 mm |
| Materials | Housing: orange PA; socket: nickel-plated brass |
| Sealing material | FKM |
| Outputs |
| Number of digital outputs | 8; (IO-Link Port Class A: 8 x 1) |
| Current rating per output | 300 mA |
| Short-circuit-proof | |
| Remarks |
| Remarks | For further information, please refer to the operating instructions. |
IO-Link-Master DataLine, 208 x 59,3 x 38,4 mm, Anzahl der digitalen Eingänge 16, Anzahl der digitalen Ausgänge 8, IP 65, IP 66, IP 67