Further information for ifm Electronic AC522A AS-i input module 2AI IP50
Accessories
Scope of delivery
Base unit
Optional accessories
Cap: M12, E73004; Impact protection: E7000A
Approvals / tests
ATEX equipment marking
II 3D Ex tc IIIB T80°C Dc X IP50
EMC
EN 50295
MTTF
174 years
AS-i parameters
AS-i version
2.11; 3.0
AS-i addressing
Addressing socket
AS-i Master profile
M3; M4
AS-i profile
S-7.3.D
AS-i I/O configuration
7 hex
AS-i ID code
3.D hex
Extended addressing mode
AS-i certificate applied for
Displays / controls
Indication
Operation / LED, green voltage AS-i; Error / LED, red; Function / LED, yellow channels AI1, AI2
Electrical connection
Module connection
Flat cable
Quick mounting technology for AS-i flat cable
; Alignment possible in three directions
Plug connection
M12; coding: A; contacts: 4
Electrical data
Operating voltage
26,5...31,6 DC V
Max. current draw from AS-i
250 mA
Reverse polarity protection
Environmental conditions
Ambient temperature
-10...50 °C
Degree of protection
IP 50
Field of application
Model
DIN rail housing
Application
AS-i ATEX module
Inputs
Sensor supply for inputs
AS-i
Number of analogue inputs
2; (connection of 2- and 3-wire sensors)
Analogue input current
4...20 mA
Resolution
12 bit
Short-circuit-proof
Inputs / Outputs
Number of inputs and outputs
Number of analog inputs: 2
Mechanical data
Housing
rectangular
Mounting method
Quick mounting; AS-i flat cable directly connectable; DIN rail mounting; (TH35 (EN 60715))
Dimensions
103 x 45 x 44,7 mm
Materials
PA; Piercing contacts: CuSn6 nickel-plated and tin-plated
Remarks
Remarks
Mechanical protection must be provided. Otherwise, the device may only be mounted together with the shock protection (E7000A). When supplying actuators from AS-i, a maximum of 200 mA may be drawn in total. There is a galvanic connection between sensor connection and AS-i.
AS-i Eingangsmodul, 103 x 45 x 44,7 mm, ClassicLine 2AI C II 3D, Steckverbindung, IP 50