| Accessories |
| Scope of delivery | Base unit |
| Optional accessories | Closure cap: M12, E73004 |
| Accuracy / Deviations |
| Accuracy | 0.5; (% of measurement range end value; tolerance under influence of electromagnetic interference: < ± 1 % of measurement range end value) |
| Approvals / tests |
| EMC | EN 50295; EN 61000-6-2; EN 61000-6-3 |
| MTTF | 105 years |
| UL approval | Power supply / Class 2 |
| AS-i parameters |
| AS-i version | 2.11; 3.0 |
| AS-i Master profile | M3; M4 |
| AS-i profile | S-7.3.E |
| AS-i I/O configuration | 7 hex |
| AS-i ID code | 3.E hex |
| AS-i certificate | 123501 |
| Extended addressing mode | |
| Displays / controls |
| Indication | Analog signal / LED, yellow channels AI1...AI4; Operation / LED, green AS-i, AUX; Fault / LED, red |
| Electrical connection |
| Module connection | Flat cable |
| Quick mounting technology for AS-i flat cable | ; Alignment possible in three directions |
| Plug connection | M12; coding: A; contacts: 4 |
| Electrical data |
| Operating voltage | 18...31,6 DC V |
| Max. current draw from AS-i | 50 mA |
| Total current rating | 2 A |
| Additional power supply | 16...30 DC; (AUX) V |
| Maximum current draw from additional supply | 2000 mA |
| Reverse polarity protection | |
| Environmental conditions |
| Ambient temperature | -25...70 °C |
| Storage temperature | -25...70 °C |
| Maximum permissible relative humidity | 90; (non-condensing) % |
| Maximum height above sea level | 2000 m |
| Degree of protection | IP 67 |
| Field of application |
| Model | DIN rail housing |
| Application | Field mounting |
| Inputs |
| Sensor supply for inputs | AUX |
| Number of analogue inputs | 4; (connection of 2- and 3-wire sensors) |
| Analogue input current | 4...20 mA |
| Maximum voltage drop across load at rated voltage | 10 V |
| Resolution | 12 bit |
| Short-circuit-proof | |
| Mechanical data |
| Housing | rectangular |
| Mounting method | DIN rail mounting; (TH35 (EN 60715)) |
| Dimensions | 103 x 45 x 44,7 mm |
| Materials | PA; Piercing contacts: CuSn6 nickel-plated and tin-plated |
| Product features |
| Number of inputs and outputs | Number of analogue inputs: 4 |
| Remarks |
| Remarks | Galvanic isolation exists between AS-i and AUX and between AS-i and the analog inputs. The power supply for sensors can be connected to pins 1 and 3. |
AS-i Eingangsmodul, 103 x 45 x 44,7 mm, ClassicLine 4AI C AUX IP67, Steckverbindung, IP 67