26.5...31.6 DC; ("supply class 2" according to cULus) V
Max. current draw from AS-i
150 mA
Additional power supply
15...30 DC; (AUX) V
Maximum current draw from additional supply
4000 mA
Integrated watchdog
Environmental conditions
Ambient temperature
-25...70 °C
Degree of protection
IP 67
Field of application
Model
DIN rail housing
Application
Field mounting
Inputs
Number of digital inputs
2
Input circuitry for digital inputs
PNP
Sensor supply for inputs
AS-i
Power supply
18...30; (via flat cable) V
Max. current rating inputs total
100 mA
Input current high
6...10 mA
Input current Low
0...2 mA
High switching level
> 11 V
Short-circuit resistance digital inputs
Inputs / Outputs
Number of inputs and outputs
Number of digital inputs: 2; Number of digital outputs: 2
Mechanical data
Housing
rectangular
Mounting method
AS-i flat cable directly connectable; DIN rail mounting; (TH35 (EN 60715))
Dimensions
103 x 45 x 44,7 mm
Materials
PA; Piercing contacts: CuSn6 nickel-plated and tin-plated
Outputs
Number of digital outputs
2
Circuitry
PNP
Voltage range DC
15...30; (according to PELV; via flat cable) V
Current rating per output
2000; (Service category DC-13 (control of electromagnets): 40 W (IEC 60947-5-1)) mA
Total output current rating
4 A
Actuator supply for outputs
AUX
Short-circuit-proof
Galvanically isolated
Remarks
Remarks
Inputs and outputs must not be connected galvanically; None of the following terminals may be connected to an external potential: I-, I+, I1, I2; The terminals are galvanically connected to the AS-i cable.
Active ClassicLine module, AS-i flat cable connection, 2 inputs / 2 outputs, Addressing socket, Three orientations of the flat cable are possible, Digital inputs and outputs (2 A), Sockets M12 x 1
Operating voltage: 26.5...31.6 V DC
Electrical design: 2 inputs / 2 outputs
Output function: transistor PNP
Total current consumption from AS-i: < 150 mA
Circuit: DC PNP
Sensor supply: AS-i
Voltage range: 18...30 DC V
Outputs:
Housing materials: PA; Piercing contacts: CuSn6 surface nickel and tin-plated
Ambient temperature: -25...70 °C
Protection: IP 67
Operation: LED green
Function display: LED yellow
Error: LED Red
Accessories (to be ordered separately): Socket, Mounting accessories