26.5...31.6 DC; ("supply class 2" according to cULus) V
Max. current draw from AS-i
300 mA
Environmental conditions
Ambient temperature
-25...70 °C
Degree of protection
IP 67
Field of application
Model
DIN rail housing
Application
Field mounting
Inputs
Number of digital inputs
8; (2 x Slave)
Input circuitry for digital inputs
PNP
Sensor supply for inputs
AS-i
Power supply
18...30 V
Max. current rating inputs total
250; (2 x 125) mA
Input current high
6...10 mA
Input current Low
0...2 mA
High switching level
> 11 V
Short-circuit resistance digital inputs
Inputs / Outputs
Number of inputs and outputs
Number of digital inputs: 8
Mechanical data
Housing
rectangular
Mounting method
AS-i flat cable directly connectable; DIN rail mounting; (TH35 (EN 60715))
Dimensions
103 x 90 x 44,2 mm
Materials
PA; Piercing contacts: CuSn6 nickel-plated and tin-plated
Remarks
Remarks
None of the following terminals may be connected to an external potential: I-, I+, I1, I2, I3, I4; The terminals are galvanically connected to the AS-i cable; Default state of ID1 codes: Slave 1=1 / Slave 2=2
Active ClassicLine module, AS-i flat cable connection, 8 digital inputs (2 slaves), Version 2.11 and 3.0 with extended addressing mode, Addressing socket, Three orientations of the flat cable are possible, Sockets M12 x 1, Digital inputs
Operating voltage: 26.5...31.6 V DC
Electrical design: 8 digital inputs (2 slaves)
Total current consumption from AS-i: < 300 mA
Circuit: DC PNP
Sensor supply: AS-i
Voltage range: 18...30 DC V
Housing materials: PA; Piercing contacts: CuSn6 surface nickel and tin-plated
Ambient temperature: -25...70 °C
Protection: IP 67
Operation: LED green
Function display: LED yellow
Error: LED Red
Accessories (to be ordered separately): Socket, Mounting accessories