| Accessories |
| Scope of delivery | Base unit |
| Optional accessories | Addressing cable: E70213; Cap: M12, E73004 |
| Approvals / tests |
| EMC | EN 62026-2; EN 61326-3-1 |
| Shock resistance | EN 60068-2-27 |
| Vibration resistance | EN 60068-2-6 |
| AS-i parameters |
| AS-i version | 2.11; 3.0 |
| AS-i addressing | Addressing socket |
| AS-i Master profile | M3; M4 |
| AS-i profile | S-7.B.E |
| AS-i I/O configuration | 7 hex |
| AS-i ID code | B.E hex |
| AS-i certificate | 126301 |
| Data bit assignment | Data bit / D0 / D1 / D2 / D3; Assignment / O1 / O2 / O3 / O4 |
| Extended addressing mode | |
| Displays / controls |
| Indication | Operation / 1 x LED, green; Fault / 1 x LED, red; Switching state / 1 x LED, yellow; Alarm / 1 x LED, red |
| Electrical connection |
| Module connection | Flat cable |
| Quick mounting technology for AS-i flat cable | ; Alignment possible in three directions |
| Electrical connection - O-3/4 |
| Plug connection | 1 x M12; Coding: A; Contacts: 3; Max. cable length: 10 m |
| Electrical data |
| Operating voltage | 26.5...31.6 DC; ("supply class 2" according to cULus) V |
| Max. current draw from AS-i | 35 mA |
| Protection class | III |
| Additional power supply | 19,2...28,8 DC V |
| Maximum current draw from additional supply | 3000; (AUX ; after SELV/PELV) mA |
| Reverse polarity protected | |
| Integrated watchdog | |
| Environmental conditions |
| Ambient temperature | -25...55 °C |
| Note on ambient temperature | with switched outputs: -25...40 °C |
| Maximum permissible relative humidity | 95 % |
| Maximum height above sea level | 2000 m |
| Degree of protection | IP 67 |
| Pollution degree | 2 |
| Field of application |
| Model | DIN rail housing |
| Application | AS-i Safety at Work |
| Inputs |
| Number of digital inputs | 2; (2 x safety input) |
| Input circuitry for digital inputs | PNP |
| Sensor supply for inputs | AUX |
| Power supply | 19,2...28,8 V |
| Max. current rating inputs total | 2000 mA |
| Input current limiting | 8 mA |
| Input current high | > 6 mA |
| Input current Low | < 2 mA |
| High switching level | > 13 V |
| Low switching level | < 5 V |
| Overload resistance digital inputs | |
| Short-circuit detection | |
| Short-circuit-proof | |
| Inputs / Outputs |
| Number of inputs and outputs | Number of digital inputs: 2; Number of digital outputs: 2 |
| Mechanical data |
| Housing | rectangular |
| Mounting method | AS-i flat cable directly connectable; DIN rail mounting; (TH35 (EN 60715)) |
| Dimensions | 103 x 45 x 44,7 mm |
| Materials | Housing: PA; piercing contacts: CuSn6 nickel-plated and tin-plated |
| Outputs |
| Output signal | Switching signal |
| Number of digital outputs | 2 |
| Voltage range DC | 19.2...28.8; (AUX) V |
| Current rating per output | 500 mA |
| Actuator supply for outputs | AUX |
| Short-circuit protection | |
| Overload resistant | |
| Galvanically isolated | |
| Remarks |
| Remarks | PL e, Cat.4, SIL 3 only if the fault exclusions described in the manual are applied |
| Safety ratings |
| Complies with requirements | ISO 13849-1 Category 4, PL e; IEC 61508 SIL 3 |
| Service life TM (additional information) | 20 years |
| PFH | 2,33E-11 1/h |