Number of digital inputs: 2; Number of digital outputs: 2
Mechanical data
Housing
rectangular
Mounting method
AS-i flat cable directly connectable; DIN rail mounting; (TH35 (EN 60715))
Dimensions
103 x 45 x 44,7 mm
Materials
PA; Piercing contacts: CuSn6 nickel-plated and tin-plated
Outputs
Number of digital outputs
2
Circuitry
PNP
Voltage range DC
15...30; (according to PELV; via flat cable) V
Current rating per output
2000; (Service category DC-13 (control of electromagnets): 40 W (IEC 60947-5-1)) mA
Short-circuit-proof
Galvanically isolated
Remarks
Remarks
A mechanical protection must be implemented.; Otherwise, the device may only be mounted together with the shock protection (E7000A).; Inputs and outputs must not be connected galvanically.; None of the following terminals may be connected to an external potential:; I-, I+, I1, I2; The terminals are galvanically connected to the AS-i cable.
Active ClassicLine module, AS-i flat cable connection, 2 inputs / 2 outputs, Addressing socket, Three orientations of the flat cable are possible, ATEX approval, Group II, category 3D, Only in conjunction with impact protection housing E7000A or equivalent protection, Digital inputs and outputs (2 A), Sockets M12 x 1
Operating voltage: 26.5...31.6 V DC
Electrical design: 2 inputs / 2 outputs
Output function: transistor PNP
Total current consumption from AS-i: < 150 mA
Circuit: DC PNP
Sensor supply: AS-i
Voltage range: 18...30 DC V
Outputs:
Housing materials: PA; Piercing contacts: CuSn6 surface nickel and tin-plated
Ambient temperature: -10...50 °C
Protection: IP 50
Operation: LED green
Function display: LED yellow
Error: LED Red
Accessories (to be ordered separately): Socket, Mounting accessories