Further information for Ifm Electronic AC506S - Safety Work flat cable connection
Accessories
Scope of delivery
Base unit
Optional accessories
Addressing cable: E70213; Cap: M12, E73004
Approvals / tests
EMC
EN 62026-2; EN 61326-3-1
AS-i parameters
AS-i version
2.11; 3.0
AS-i addressing
Addressing socket
AS-i Master profile
M3; M4
AS-i profile
S-7.B.E
AS-i I/O configuration
7 hex
AS-i ID code
B.E hex
AS-i certificate
97201
Extended addressing mode
Displays / controls
Indication
Operation / 1 x LED, green; Fault / 1 x LED, red; Switching state / 1 x LED, yellow; Alarm / 1 x LED, red
Electrical connection
Module connection
Flat cable
Quick mounting technology for AS-i flat cable
; Alignment possible in three directions
Electrical connection - Socket 1A
Plug connection
1 x M12; coding: A; contacts: 4; max. cable length: 10 m
Electrical data
Operating voltage
26.5...31.6 DC; ("supply class 2" according to cULus) V
Electricity consumption
< 280 mA
Current rating per module / socket
0,2 A
Integrated watchdog
Environmental conditions
Ambient temperature
-25...55 °C
Note on ambient temperature
with switched outputs: -25...40 °C
Maximum height above sea level
2000 m
Degree of protection
IP 67
Pollution degree
2
Field of application
Model
DIN rail housing
Application
AS-i Safety at Work
Inputs
Number of digital inputs
4; (2 x 2 safety inputs)
Input circuitry for digital inputs
PNP
Sensor supply for inputs
AS-i
Max. current rating inputs total
200 mA
Input current [mA]
8
Short-circuit detection
Short-circuit-proof
Inputs / Outputs
Number of inputs and outputs
Number of digital inputs: 4; Number of digital outputs: 2
Mechanical data
Housing
rectangular
Mounting method
AS-i flat cable directly connectable; DIN rail mounting; (TH35 (EN 60715))
Dimensions
103 x 45 x 44,7 mm
Materials
Housing: PA; piercing contacts: CuSn6 nickel-plated and tin-plated
Outputs
Output signal
Switching signal
Number of digital outputs
2
Voltage range DC
18...30; (AS-i) V
Current rating per output
50 mA
Actuator supply for outputs
AS-i
Galvanically isolated
Remarks
Remarks
PL d, Cat.3, SIL 2 only if fault exclusions described in the manual are applied
Safety ratings
Complies with requirements
ISO 13849-1 Category 3, PL d; IEC 61508 SIL 2
Service life TM (additional information)
20 years
PFH
2,4 E-11 1/h
AS-i Safety at Work, AS-i flat cable connection, 2x2 safe inputs / 2 non-safe LED outputs / 2 non-safe outputs, Safe AS-i input module 4SI / 2DO T / 2LO, Addressing socket, Three orientations of the flat cable are possible, Sockets M12 x 1
Operating voltage: 26.5...31.6 V DC
Electrical design: 2x2 safe inputs / 2 non-safe LED outputs / 2 non-safe outputs
Circuit: DC PNP
Sensor supply: AS-i
Outputs:
Housing materials: PA; Piercing contacts: CuSn6 surface nickel and tin-plated
Ambient temperature: -25...55, -25...40 °C with switched outputs °C
Protection: IP 67
Operation: LED green
Function display: LED yellow
Error: LED Red
Accessories (to be ordered separately): Socket, Mounting accessories