| Approvals / tests |
| EMC | EN 50295 |
| MTTF | 145 years |
| AS-i parameters |
| AS-i Master profile | M3; M4 |
| AS-i profile | S-7.3.5 |
| AS-i I/O configuration | 7 hex |
| AS-i ID code | 3.5 hex |
| Displays / controls |
| Indication | analogue signal / LED, yellow channels AO1...AO2; operation / LED, green AS-i, AUX; fault / LED, red |
| Electrical connection |
| Module connection | Flat cable |
| Electrical data |
| Operating voltage | 26,5...31,6 DC V |
| Max. current draw from AS-i | 140 mA |
| Additional power supply | 24...30 DC; (AUX) V |
| Maximum current draw from additional supply | 550; (AUX) mA |
| Reverse polarity protection | |
| Environmental conditions |
| Ambient temperature | 0...70 °C |
| Storage temperature | -25...85 °C |
| Maximum permissible relative humidity | 90; (non-condensing) % |
| Maximum height above sea level | 2000 m |
| Degree of protection | IP 65 |
| Field of application |
| Application | Field mounting |
| Inputs |
| Accuracy | 0,5 % |
| Inputs / Outputs |
| Number of inputs and outputs | Number of analogue outputs: 2 |
| Mechanical data |
| Housing | rectangular |
| Mounting method | AS-i interface to FK-E subunits |
| Dimensions | 102 x 91 x 71 mm |
| Materials | Housing: PBT |
| Outputs |
| Number of analogue outputs | 2; (connection of 2- or 4-wire actuators) |
| Analog output voltage | 0...10 V |
| Minimum load resistance | 3300 Ω |
| Analog output resolution | 16 (1 bit = 1 mV) |
| Actuator supply for outputs | AS-i / AUX |
| Overload resistant | |
AS-i Ausgangsmodul, 102 x 91 x 71 mm, UniversalModule 2AO(V) IP65, Anschlussklemmen, IP 65