| Accessories |
| Optional accessories | Connector plug |
| Approvals / tests |
| EMC | EN 61000-6-2; EN 62026-2; EN 50581 |
| MTTF | 325 years |
| AS-i parameters |
| AS-i version | 2.11; 3.0 |
| AS-i addressing | Addressing socket |
| AS-i profile | S-7.A.E |
| AS-i I/O configuration | 7 hex |
| AS-i ID code | A.E hex |
| Data bit assignment | Data bit / D0 / D1 / D2 / D3; Input / I-1 / I-2 / I-3 / I-4; Output / O-1 / O-2 / - / - |
| Extended addressing mode | |
| AS-i certificate applied for | |
| Displays / controls |
| Indication | Switching state / LED, yellow I1...I4, O1...O4; Operation / LED, green AS-i; Fault / LED, red |
| Electrical data |
| Operating voltage | 26,5...31,6 DC V |
| Max. current draw from AS-i | 250 mA |
| Integrated watchdog | |
| Environmental conditions |
| Ambient temperature | -25...60 °C |
| Maximum permissible relative humidity | 90; (non-condensing) % |
| Maximum height above sea level | 2000 m |
| Degree of protection | IP 20 |
| Pollution degree | 2 |
| Field of application |
| Model | DIN rail housing |
| Application | Control cabinet mounting |
| Inputs |
| Number of digital inputs | 4 |
| Input circuitry for digital inputs | PNP; (Type 2 according to IEC 61131-2) |
| Sensor supply for inputs | AS-i |
| Power supply | 18...30; (DC) V |
| Max. current rating inputs total | 200 mA |
| Input current high | 6...10 mA |
| Input current Low | 0...2 mA |
| High switching level | > 11 V |
| Short-circuit resistance digital inputs | |
| Inputs / Outputs |
| Number of inputs and outputs | Number of digital inputs: 4; Number of relay outputs: 2 |
| Mechanical data |
| Housing | rectangular |
| Mounting method | DIN rail mounting; (TH35 (EN 60715)) |
| Dimensions | 93 x 25,4 x 108 mm |
| Materials | PC-GF20 |
| Outputs |
| Voltage range DC | 24 V |
| AC voltage range | 10...240 V |
| Current rating per output | 6000; (240 V AC; 24 V DC; resistive load) mA |
| Total output current rating | 6; (240 V AC; 24 V DC; ohmic load) A |
| Number of relay outputs | 2 |
| Contact rating | 6 A; (max. 240 V AC / 24 V DC see diagram: Contact load capacity Normally open contact (NO): B300: 6000 cycles) |
| Short-circuit-proof | |
| Galvanically isolated | |
AS-i Eingangs-/Ausgangsmodul, 108 x 25 x 105 mm, SmartL25 4DI 2DO R C, Anschlussklemmen, IP 20