Further information for Ifm Electronic AC2254 - Active module Mounting DIN rail
Accessories
Optional accessories
Connector plug
Approvals / tests
EMC
EN 61000-6-2; EN 62026-2; EN 50581
MTTF
485 years
Notes
The device must be powered from a galvanically isolated voltage source. This voltage source must be secondary-protected by a UL-approved fuse (see appendix). Alternatively, a Class 2 power supply may also be used to power AUX.
AS-i parameters
AS-i version
2.11; 3.0
AS-i addressing
Addressing socket
AS-i Master profile
M2; M3; M4
AS-i profile
S-0.A.E
AS-i I/O configuration
0 hex
AS-i ID code
A.E hex
AS-i certificate
39402
Data bit assignment
Data bit / D0 / D1 / D2 / D3; Input / I-1 / I-2 / I-3 / I-4
Extended addressing mode
Displays / controls
Indication
Switching state / LED, yellow I1...I4; Operation / LED, green AS-i, AUX; Fault / LED, red
Electrical data
Operating voltage
26,5...31,6 DC V
Max. current draw from AS-i
50 mA
Additional power supply
20...30 DC; (AUX) V
Maximum current draw from additional supply
600; (AUX) mA
Environmental conditions
Ambient temperature
-25...70 °C
Maximum permissible relative humidity
90; (non-condensing) %
Maximum height above sea level
2000 m
Degree of protection
IP 20
Pollution degree
2
Field of application
Model
DIN rail housing
Application
Control cabinet mounting
Inputs
Number of digital inputs
4
Input circuitry for digital inputs
PNP; (Type 2 according to IEC 61131-2)
Sensor supply for inputs
AUX
Power supply
18...30; (DC) V
Max. current rating inputs total
500 mA
Input current high
6...10 mA
Input current Low
0...2 mA
High switching level
> 11 V
Short-circuit resistance digital inputs
Inputs / Outputs
Number of inputs and outputs
Number of digital inputs: 4
Mechanical data
Housing
rectangular
Mounting method
DIN rail mounting; (TH35 (EN 60715))
Dimensions
93 x 25,4 x 108 mm
Materials
PC-GF20
Active AS-i module, Mounting on DIN rail, 4 inputs, String mounting possible, Addressing socket, Input supply from external PELV voltage source, Version 2.1 with extended addressing mode, Combicon connection, Digital inputs
Operating voltage: 26.5...31.6 V DC
Electrical design: 4 inputs
Total current consumption from AS-i: < 50 mA
Circuit: PNP
Sensor supply: via E+/E- / external to PELV
Voltage range: 20...30 DC V
Connection: Combicon
Housing materials: PA
Ambient temperature: -25...70, cRUus: surrounding air temperature -25...60 °C °C
Protection: IP 20
Operation: LED green
Error: LED Red
Accessories (to be ordered separately): Mounting accessories