Operation / LED, green (AS-i); switching state / LED, yellow (I1...I4, O3...O4)
Electrical connection
Module connection
Flat cable
Electrical connection - Socket I-1/2
Plug connection
M12; coding: A; contacts: 4
Electrical data
Operating voltage
26,5...31,6 DC V
Max. current draw from AS-i
170 mA
Integrated watchdog
Environmental conditions
Ambient temperature
0...55 °C
Note on ambient temperature
With special compressed air treatment: < 0 °C; At ambient temperatures > 50 °C, derating of current loading capacity must be considered as per operating instructions
Storage temperature
-20...80 °C
Maximum permissible relative humidity
90; (non-condensing) %
Maximum height above sea level
2000 m
Degree of protection
IP 67
Pollution degree
2
Field of application
Application
Field mounting; For use in wet environments
Inputs
Number of digital inputs
4; (2 x 2)
Input circuitry for digital inputs
PNP
Sensor supply for inputs
AS-i
Power supply
20...30 V
Max. current rating inputs total
100 mA
Input current high
> 3 mA
Input current Low
< 1,5 mA
High switching level
> 10 V
Short-circuit resistance digital inputs
Inputs / Outputs
Number of inputs and outputs
Number of digital inputs: 4; number of pneumatic outputs: 2
Please note the instructions regarding compressed air and EMC/ESD under "Downloads"
AS-i AirBox, AS-i interface to FC lower parts, 2 x 2 inputs / 2 outputs, Connection to the pneumatic system by tube fittings, Manual override by pressing/releasing or pressing/turning/locking, 2 x 2 digital inputs, Sockets M12 x 1, 2 pneumatic outputs
Operating voltage: 26.5...31.6 V DC
Electrical design: 2 x 2 inputs / 2 outputs
Output function: common exhaust with tube connection
Total current consumption from AS-i: < 170 mA
Circuit: DC PNP
Sensor supply: AS-i
Voltage range: 20...30 DC V
Outputs:
Pneumatic system: two 3/2-way valves
Operating pressure range: 2...8 [bar]
Connection: contact pins on FC or SC lower module
Housing materials: housing: PBT; Metal parts: stainless steel (303S22); sealing: Viton
Ambient temperature: 0...55, use below 0 °C possible with a special compressed air treatment °C
Protection: IP 67
Operation: LED green
Function display: LED yellow
Accessories (to be ordered separately): Socket, Mounting accessories