Further information for Ifm Electronic AC1253 - Power supply Three phase power supply
380 480 AC
Approvals / tests
EMC
EN 61000-6-1; EN 61000-6-2; EN 61000-6-3; EN 61000-6-4
Vibration resistance
IEC 60068-2-6 / ± 1.6 mm 2...17.8 Hz / 2 g 17.8...500 Hz
Shock resistance
IEC 60068-2-27 / 30 g 6 ms / 20 g 11 ms
Power factor correction PFC
complies
AS-i parameters
AS-i certificate
98401
Displays / controls
Indication
AS-i voltage / LED, green
Electrical data
AC frequency
47...64 Hz
Operating voltage tolerance
15...20 %
Nominal voltage AC
400 V
Input voltage range AC
380...480 V
Protection class
I
Over voltage protection
ja; (< 36 V)
Max. standby delay time
90 ms
Output voltage AS-i
30,5 V
Output power (continuous)
244 W
Output power (temporary)
256 W
Note on output power (temporary)
Briefly, for charging the bus capacitances after power-on W
Power factor (rated voltage 400 V AC / 50 Hz)
0,53
Power factor (rated voltage 480 V AC / 50 Hz)
0,52
Power reserve
5 %
Number of output circuits
1
Output current AS-i
8 A
Max. ripple
90 mV
Inrush current (rated voltage 400 V AC / 60 Hz)
4 A
Inrush current (rated voltage 480 V AC / 50 Hz)
4 A
Efficiency (rated voltage 400 V AC / 60 Hz)
92 %
Efficiency (rated voltage 480 V AC / 50 Hz)
92,1 %
External input fuse
≤ B-6 A / ≤ C-3 A
Derating
6 (60...70 °C) W/K
Power failure bridging time (nominal voltage 400 V AC / 60 Hz)
34 ms
Power outage bridging time (nominal voltage 480 V AC / 50 Hz)
53 ms
Input current (rated voltage 400 V AC / 60 Hz)
0,7 A
Input current (rated voltage 480 V AC / 50 Hz)
0,6 A
Power loss (rated voltage 400 V AC / 60 Hz)
21,2 W
Power loss (rated voltage 480 V AC / 50 Hz)
20,9 W
Reverse voltage withstand
35 V
Integrated data decoupling
Environmental conditions
Ambient temperature
-25...70 °C
Note on ambient temperature
Allow for free spaces for convection (see operating instructions)
Storage temperature
-40...85 °C
Maximum permissible relative humidity
95; (IEC 60068-2-30) %
Degree of protection
IP 20
Pollution degree
2; (IEC 62103: conductive pollution not permitted)
Field of application
Model
DIN rail housing
Mechanical data
Housing
rectangular
Mounting method
DIN rail mounting; (TH35 (EN 60715))
Dimensions
130,5 x 62 x 124,3 mm
Materials
steel sheet
Outputs
Overload behaviour
constant output current
Short-circuit-proof
Overload resistant
Parallel connection of outputs possible
Series connection of outputs possible
Power supply, Three-phase AS-i power supply, 380...480 V AC, Integrated data decoupling, AS-i switch power supplies
Application: AS-i system voltage for masters, sensors, actuators and modules
Nominal voltage: 3 x 400 AC V
Nominal frequency: 50 / 60 Hz
Efficiency: 92 (400 V AC; 50 Hz) / 92.1 (480 V AC; 60 Hz) %
Connection: screw terminals
Housing materials: steel sheet
Ambient temperature: -25...70, observe the free space for convection (see operating instructions) °C
Protection: IP 20
Function display: LED green (indication AS-i voltage)
Accessories (to be ordered separately): Mounting accessories