26.5...31.6 DC; ("supply class 2" according to cULus) V
Electricity consumption
< 200 mA
Total current rating
3 A
Environmental conditions
Ambient temperature
-25...55 °C
Degree of protection
IP 20
Field of application
Model
DIN rail housing
Application
Safe actuator control
Inputs
Number of digital inputs
4
Input circuitry for digital inputs
PNP
Sensor supply for inputs
AS-i
Power supply
18...30 V
Short-circuit detection
Inputs / Outputs
Number of inputs and outputs
Number of digital inputs: 4; Number of relay outputs: 1
Mechanical data
Housing
rectangular
Mounting method
DIN rail mounting; (TH35 (EN 60715))
Dimensions
108 x 25 x 105 mm
Materials
Housing: PA
Outputs
Output signal
LED: signalling
Number of relay outputs
1; (safe relay output)
Actuator supply for outputs
AS-i
Remarks
Remarks
For further information, please refer to the operating instructions.
Safety ratings
Complies with requirements
ISO 13849-1 PL e; IEC 61508 SIL 3
Service life TM (Mission Time)
175200 h
Service life TM (additional information)
20 years
PFH
3,3E-9 1/h
PFD
9,25E-6
Safe active AS-i output module, Mounting on DIN rail, 4 non-safe inputs, 2 non-safe LED outputs, 1 safe relay output, SIL 3 to EN 62061, IEC 61508 / , SIL 3 and EN ISO 13849 - 1 / PL e, for the safe triggering of actuators, Combicon connection
Operating voltage: 26.5...31.6 V DC
Electrical design: 4 non-safe inputs, 2 non-safe LED outputs, 1 safe relay output
Circuit: DC PNP
Voltage range: 18...30 DC V
Connection: Combicon
Housing materials: PA
Ambient temperature: -25...55 °C
Protection: IP 20
Operation: LED green
Function display: LED yellow
Error: LED Red
Accessories (to be ordered separately): Mounting accessories