Switching state / LED, yellow SI1...SI2, O3...O4; Operation / LED, green AS-i; Fault / LED, red ERR O1...O2
Electrical connection
Pin headers
4 x ; pitch: 5.0 mm
Electrical data
Operating voltage
26,5...31,6 DC V
Max. current draw from AS-i
250 mA
Total current rating
6; (resistive load) A
Integrated watchdog
Environmental conditions
Ambient temperature
-25...50 °C
Storage temperature
< 80 °C
Maximum permissible relative humidity
80; (non-condensing) %
Maximum height above sea level
2000 m
Degree of protection
IP 20
Pollution degree
2
Field of application
Model
DIN rail housing
Application
Control cabinet mounting
Inputs
Number of digital inputs
2; (2 x safety input)
Input circuitry for digital inputs
PNP; (DC)
Sensor supply for inputs
AS-i
Max. current rating inputs total
100 mA
Input current high
10 mA
Short-circuit protection digital inputs
Inputs / Outputs
Number of inputs and outputs
Number of digital inputs: 2; Number of relay outputs: 2
Mechanical data
Housing
rectangular
Mounting method
DIN rail mounting; (TH35 (EN 60715))
Dimensions
93 x 25,4 x 108 mm
Materials
PC-GF20
Outputs
Voltage range DC
24; (Outputs O3 + O4 must be supplied pairwise with the same voltage. 2 x 24 V DC) V
AC voltage range
10...240; (Outputs O3 + O4 must be supplied with the same voltage in pairs. 2 x 240 V AC) V
Current rating per output
6000; (resistive load) mA
Number of relay outputs
2
Short-circuit-proof
Galvanically isolated
Safety ratings
Complies with requirements
ISO 13849-1 Category 4, PL e; IEC 61508 SIL 3
Service life TM (Mission Time)
175200 h
Service life TM (additional information)
20 years
PFH
4E-09 1/h
Sicheres aktives AS-i-Modul, Tragschienenmontage, 2 sichere Eingänge / 2 nicht sichere LED-Ausgänge / 2 nicht sichere Relaisausgänge, Performance Level e , gemäß EN ISO 13849-1 , und IEC 61508 / SIL 3, zum Anschluss von mechanischen Kontakten, Combicon Anschluss
Betriebsspannung: 26,5...31,6 V DC
Elektrische Ausführung: 2 sichere Eingänge / 2 nicht sichere LED-Ausgänge / 2 nicht sichere Relaisausgänge
Beschaltung: DC PNP
Sensorversorgung: AS-i
Ausgänge:
Anschluss: Combicon
Gehäusewerkstoffe: PA
Umgebungstemperatur: -25...50 °C
Schutzart: IP 20
Betrieb: LED grün
Funktionsanzeige: LED gelb
Fehler: LED rot
Zubehör (separat bestellen): Montagezubehör
Fabrikat: ifm electronic gmbh oder gleichwertig
Typ: AC009S