Technical data:
Special PVC hose cable in accordance with UL CSA AWM I/II A/B Style 2587 (jacket material) and CSA
Temperature range moving -5°C to +90°C fixed -40°C to +90°C
Nominal voltage UL/CSA 600 V
Test voltage 3000 V
Breakdown voltage min. 6000 V
Insulation resistance min. 20 MOhm x km
Minimum bending radius moving 10x cable Ø fixed 5x cable Ø
Radiation resistance up to 80x106 cJ/kg (up to 80 Mrad)
Coupling resistance max. 250 Ohm/km
Structure:
Bare copper conductor, finely stranded in accordance with DIN VDE 0295 cl.5, BS 6360 cl.5 and IEC 60228 cl.5
Core insulation made of PVC compound type TI3 in accordance with DIN VDE 0207-363-3 / DIN EN 50363-3 and class 43 according to UL Std.1581
Core identification according to DIN VDE 0293 black cores with continuous white numbering
Cores stranded in layers with optimal lay lengths
PVC inner jacket YM5 according to DIN VDE 0207 Part 5
Shielding braid made of tinned copper wires, coverage approx. 85%
Outer jacket made of special PVC compound type YM5 according to DIN VDE 0207 Part 5 and class 43 according to UL Std.1581
Jacket color: gray (RAL 7001) with meter marking
Properties:
Resistant to mineral oils, synthetic oils and coolants.
The outer jacket passes an improved oil resistance test.
The materials used in production are silicone and cadmium-free and free from substances that impair the wetting properties of paint.
Tests:
PVC self-extinguishing and flame-retardant in accordance with DIN VDE 0482-332-1-2, DIN EN 60332-1-2, IEC 60332-1-2, UL VW-1, CSA FT1
Notes:
'Cleanroom qualified\lashunshielded analogue type: JZ-602
Use:
UL and CSA approved flexible control cables up to 600 V, for all machines in tool and plant construction, suitable for installation in dry, damp and wet rooms with medium mechanical stress without tensile stress and without forced movement, but not outdoors. Designed for export-oriented machine builders, especially for the USA and Canada. EMC = Electromagnetic Compatibility To optimise the EMC properties, we recommend contacting the copper braid on both sides and over a large area all around.
Standard lengths: 100 m, 500 m, 1000 m