Further information for Helukabel 75009 - HELU THERMFLEX® 180 EWKF 3G2 5qmm Black Heat resistant cable
Technical data:
based on DIN VDE 0285-525-2-83/ DIN EN 50525-2-83
Temperature range moving -25°C to +180°C fixed -60°C to +180°C
Nominal voltage U0/U 300/500 V
Test voltage 2000 V
Insulation resistance min. 200 MOhm x km
Minimum bending radius moving 7.5x cable Ø fixed 4x cable Ø
Radiation resistance up to 20x106 cJ/kg (up to 20 Mrad) Tests:
Insulation integrity tested according to DIN VDE 0472 Part 814 and IEC 60331
Halogen-free according to DIN VDE 0482 Part 267, DIN EN 50267-2-1, IEC 60754-1 (corresponds to DIN VDE 0472 Part 815)
Burning behaviour none Fire propagation according to DIN VDE 0482-332-1-2, DIN EN 60332-1-2, IEC 60332-1
Corrosivity of fire gases according to DIN VDE 0482 Part 267, DIN EN 50267-2-2, IEC 60754-2 (corresponds to DIN VDE 0472 Part 813)
Structure:
Tinned copper wire, according to DIN VDE 0295 cl.5, fine-wire, BS 6360 cl.5, IEC 60228 cl.5
Core insulation made of special silicone rubber compound type EI2 according to DIN VDE 0207-363-1 / DIN EN 50363-1
Core identification according to DIN VDE 0293-308 with white number print
Cores stranded in layers with optimal lay lengths
Outer sheath made of Special silicone rubber mixture type 2GM1 according to DIN VDE 0207-363-2-1/DIN EN 50363-2-1
Sheath color: black (RAL 9005) with meter marking
Properties:
low smoke density
due to the particularly abrasion and notch-resistant sheath, these cables can withstand much greater mechanical stress than normal silicone cables and thus have a significantly longer service life
hardly any changes in the dielectric strength and insulation resistance even at higher temperatures
high flash point
leaves insulating SiO2 in the event of a fire, thus ensuring longer functional integrity
Resistant to high molecular oils, vegetable and animal fats, alcohols, plasticizers and clophen, diluted acids, alkalis and salt solutions, oxidizing agents, tropical and weather influences, sea water, oxygen, ozone
Notes:
EWKF = improved values for tear resistance, tear propagation resistance, notch resistance, flexibility
shielded analogue type: THERMFLEX 180 EWKF-C
Use:
This type of cable has proven itself wherever it is exposed to increased mechanical stress, as well as where cable insulation is exposed to high temperatures. For use in dry, damp and wet rooms, as well as outdoors. Silicone cables are halogen-free and are suitable for use in air conditioning and heating technology, for lighting fixtures, for cabling ovens, in saunas and solariums, in foundries, in steel, cement and ceramics works and in heating and cooling technology. FRNC = Flame Retardant Non Corrosive All silicone cables are also available in FRNC design. With this special sheath mixture, test type C in accordance with VDE 0472 Part 804 and IEC 60332-3 or HD 405.3 is met for flame retardancy. This sheath mixture is self-extinguishing. The cable can therefore also be used as a safety cable with functional integrity - e.g. E.g. in public buildings, power plants, hotels, airports, etc.
Standard lengths: 100 m, 500 m, 1000 m
Subject to technical changes.