Further information for Helukabel 24030
			
			
Technical data:
Special PVC hose cable with increased heat resistance based on DIN VDE 0285-525-2-11 / DIN EN 50525-2-11 0.5-0.75 mm² in accordance with IEC 60227/56 1.0-2.5 mm² in accordance with IEC 60227/57
Temperature range moving -5°C to +105°C fixed -30°C to +105°C (briefly +120°C)
Nominal voltage 0.5-1 mm² U0/U 300/500 V from 1.5 mm² U0/U 450/750 V
Spark test 6000 V
Test voltage 2000 V
Breakdown voltage min. 4000 V
Insulation resistance min. 20 MOhm x km
Minimum bending radius moving 7.5x cable Ø fixed 4x cable Ø
Radiation resistance up to 80x106 cJ/kg (up to 80 Mrad)
Structure:
Bare copper wire, according to DIN VDE 0295 cl.5, fine-wire, BS 6360 cl.5, IEC 60228 cl.5
Core insulation made of special PVC compound type TI3 according to DIN VDE 0207-363-3 / DIN EN 50363-3 Core
identification according to DIN VDE 0293-308 with white number print
Cores stranded in layers with optimal lay lengths
Outer jacket made of heat-resistant special PVC, compound type TM3 according to DIN VDE 0207-363-4-1/DIN EN 50363-4-1
Jacket color black (RAL 9005) with meter marking
Properties:
The materials used in production are silicone and cadmium-free and free from substances that impair paint wetting
Tests:
PVC self-extinguishing and flame-retardant in accordance with DIN VDE 0482-332-1-2, DIN EN 60332-1-2, IEC 60332-1
Use:
As a connecting cable for medium mechanical stress for flexible use with free movement without tensile stress and without forced movement in dry, damp, wet rooms and outdoors, to machines, devices or systems or motors, transformers in the immediate vicinity of which increased temperatures occur (e.g. painting and drying lines).
Standard lengths: 100 m, 500 m, 1000 m
Subject to technical changes.