Technical data:
Special silicone hose cable with increased heat resistance according to UL Style 4476 and CSA AWM II A/B
Temperature range VDE -60°C to +180°C (briefly +220°C) UL/CSA -50°C to +150°C
Nominal voltage VDE U0/U 300/500 V UL/CSA 600 V
Test voltage 2000 V
Breakdown voltage min. 5000 V
Insulation resistance min. 200 MOhm x km
Minimum bending radius moving 7.5x cable Ø fixed 4x cable Ø
Radiation resistance up to 20x106 cJ/kg (up to 20 Mrad)
Structure:
Tinned copper wire, according to DIN VDE 0295 cl.5, BS 6360 cl.5 or IEC 60228 cl.5
Wire insulation made of silicone rubber
Core identification in accordance with DIN VDE 0293-308 coloured or black cores with continuous white numbering
for 2 cores brown, blue
cores stranded in layers with optimum lay lengths
Outer jacket made of silicone rubber
Jacket colour: black
Properties:
Advantages hardly any changes in dielectric strength and insulation resistance even at higher temperatures, high flash point, leaves insulating SiO2 in the event of a fire
Resistant to high molecular oils, vegetable and animal fats, alcohols, plasticisers and clophenes, diluted acids, alkalis and salt solutions, oxidising agents, tropical and weather influences, sea water, oxygen, ozone
Halogen-free in accordance with DIN VDE 0482 Part 267/ DIN EN 50267-2-1/IEC 60754-1 (corresponds to DIN VDE 0472 Part 815)
Burning behaviour no fire propagation Conductivity in accordance with DIN VDE 0482-332-1-2, DIN EN 60332-1-2, IEC 60332-1, CSA FT1
If installed permanently, only install in open, ventilated pipe systems or ducts. Otherwise, the mechanical properties of silicone will be reduced if there is no air in combination with temperatures above 90°C.
Notes:
shielded analogue type: SiHF-C-Si UL/CSA
Use:
UL and CSA approved silicone hose cable. Designed for export-oriented machine builders, especially for the USA and Canada. Silicone cables are halogen-free and are particularly suitable for use in power plants. Silicone cables have also proven themselves in iron and steel works, steel and rolling mills, solariums and saunas, foundries, in aircraft construction and shipbuilding, as well as in cement, glass and ceramics factories, in spotlights and high-performance lights and heating devices of all kinds. Due to the elastic properties of the core insulation, they are used as flexible connection cables.
Standard lengths: 500 m, 1000 m
Technical changes reserved.