Further information for Helukabel 22299 - HELU H05SS 3G1 5qmm Black Heat resistant cable
Technical data:
heat-resistant hose cable according to DIN VDE 0285-525-2-83 / DIN EN 50525-2-83
Temperature range fixed -60°C to +180°C (briefly +250°C)
permissible operating temperature on the conductor 180°C
Nominal voltage U0/U 300/500 V
Test voltage 2000 V
Specific volume resistance min. 200 MOhm x km
Minimum bending radius fixed 7.5x cable Ø 4x cable Ø
Radiation resistance up to 20x106 cJ/kg (up to 20 Mrad)
Structure:
Tinned copper wire, according to DIN VDE 0295 cl.5, fine-wire, BS 6360 cl.5, IEC 60228 cl.5
Core insulation made of cross-linked rubber (SiR) compound type EI2 according to DIN VDE 0207-363-1 / DIN EN 50363-1
Core identification according to DIN VDE 0293-308
Cores twisted in layers with optimal lay lengths
Outer jacket made of cross-linked rubber compound type EM9 according to DIN VDE 0207-363-2-1/DIN EN 50363-2-1
Jacket color: black (RAL 9005)
Braid made of polyester threads
Properties:
Hardly any changes in dielectric strength and insulation resistance even at higher temperatures.
This cable can be damaged if pulled over sharp edges or by abrasion. To avoid this during installation and use, non-braided cables in particular should be handled with care. Contact should be avoided when operating at high temperatures.
Tests:
Fire behavior Testing of vertical flame spread in accordance with DIN VDE 0482-332-1-2, DIN EN 60332-1-2, does not apply to cables with an outer polyester braid (H05SST-F)
Use:
Heat-resistant hose cables with SiR sheathing without strain relief element are used at high temperatures or when in contact with hot surfaces. For fixed installation in and on lights in industrial applications with mechanically protected installation. Recommended for use on devices that are moved during use and are subject to low mechanical loads.
Standard lengths: 100 m, 500 m, 1000 m
Subject to technical changes.