Further information for Helukabel 14056 control cable 18x1.5 mm² blue
General
Degree of protection
intrinsically safe Ignition type -i-
Temperature range in motion
-10 °C to +80 °C
Temperature range for fixed installation
-40 °C to +80 °C
Rated voltage U0/U
300/500 V
Test voltage
3000 V
Dielectric strength
min. 6000 V
Operating capacitance core/core
ca. 140 nF/km
Operating capacitance core/shield
ca. 187 nF/km
Inductance
ca. 0,68 mH/km
Coupling resistance
max. 250 Ohm/km
Minimum bending radius moving
10x Conductor Ø
Minimum bending radius not moved
5x Conductor Ø
Radiation resistance
up to 80x10⁶ cJ/kg
Conductor marking
black conductors with continuous white digit marking
Shield braid
Tinned Cu wires, coverage approx. 85%
Outer sheath
special PVC, blue (RAL 5015)
Substances interfering with paint adhesion
free of
Regulation lengths
500 m, 1000 m
Meter marking
Oil- and chemical-resistant
Silicone- and cadmium-free
Self-extinguishing and flame retardant
The Helukabel control cable type 14056 is a flexible, intrinsically safe hose cable for use in explosive atmospheres. It is marked as ignition type -i- and is used in measurement and control systems that are not earthed and have a separate circuit. The cable is specifically designed for the transmission of control and measurement signals, with shielding ensuring precise data transmission. The blue outer sheath (RAL 5015) identifies the cable as intrinsically safe according to DIN EN 60079-14 section 16.2.2 (VDE 0165 part 1). The cable is not suitable for direct burial.
Applications
Cable 14056 is used in industrial applications, particularly in areas where explosion hazards exist, such as in the chemical, petrochemical, or process industries. It is intended for use in intrinsically safe systems that fulfill a special safety function by not creating an ignition source for flammable atmospheres in case of failure. The cable is suitable for both movable and fixed installations, with temperature ranges varying depending on the mode of operation.
Functions and Features in Detail
The cable features a bare Cu conductor manufactured according to DIN VDE 0295 class 5, BS 6360 class 5, and IEC 60228 class 5. The conductors are insulated with special PVC and marked according to DIN VDE 0293, with black conductors having a continuous white numerical print. The conductors are stranded in layers with optimal lay lengths to minimize mechanical stress. A separator foil ensures clear separation between conductor layers. The shielding braid consists of tinned copper wires with approximately 85% coverage, ensuring high electromagnetic compatibility (EMC). The outer sheath is made of special PVC and is blue in color (RAL 5015), with an integrated meter marking.
Technology Explained Simply
The cable is manufactured in accordance with DIN VDE 0285-525-2-51 and DIN EN 50525-2-51. The rated voltage is 300/500 V, the test voltage is 3000 V, and the breakdown voltage is at least 6000 V. The operating capacitance between conductors is approximately 140 nF/km, and between conductor and shield is approximately 187 nF/km. The inductance is approximately 0.68 mH/km, and the coupling resistance is maximum 250 Ohm/km. The radiation resistance is up to 80x10⁶ cJ/kg (80 Mrad), ensuring suitability for environments with ionizing radiation. The temperature ranges are between -10 °C and +80 °C for movable installations, and between -40 °C and +80 °C for fixed installations. The minimum bending radius is 10 times the cable diameter for movable use and 5 times for fixed installations. The materials used are silicone- and cadmium-free and free of substances that impair lacquer adhesion.
Compatibility and Accessories
The cable is designed for use in intrinsically safe systems and meets the requirements for ignition type -i- according to DIN EN 60079-14. The shielding ensures high EMC, with bilateral and extensive full-contact grounding of the copper braid recommended to optimize EMC properties. The cable is not suitable for direct burial. The materials used are largely oil- and chemical-resistant, increasing suitability for industrial environments with aggressive media. The PVC insulation is self-extinguishing and flame-retardant according to DIN VDE 0482-332-1-2, DIN EN 60332-1-2, and IEC 60332-1-2.
Installation and Mounting
Installation is carried out in explosive atmospheres according to the requirements of DIN EN 60079-14. The cable is suitable for both movable and fixed applications. For movable installations, a minimum bending radius of 10 times the cable diameter must be maintained; for fixed installations, 5 times the cable diameter. The meter marking facilitates length measurement and positioning. Bilateral and extensive grounding of the shielding braid is recommended to maximize EMC properties.
Operational Advantages
The cable offers high mechanical and thermal load capacity, is largely oil- and chemical-resistant, and features excellent EMC. The intrinsically safe design ensures safety in explosive atmospheres. The self-extinguishing and flame-retardant PVC insulation increases fire safety. The meter marking facilitates handling and installation. Radiation resistance up to 80 Mrad makes the cable suitable for applications in radiation-exposed environments.