Further information for Helukabel 14035-1000 OZ-BL-CY control cable 18x0,75 mm² blue
General
Degree of protection
intrinsically safe (ignition type -i-)
Nominal voltage
300/500 V
Test voltage
3000 V
Dielectric strength
min. 6000 V
Operating capacitance core/core
ca. 140 nF/km
Operating capacitance core/shield
ca. 187 nF/km
Inductance
ca. 0,68 mH/km
Coupling resistance
max. 250 Ohm/km
Minimum bending radius moving
10x cable Ø
Minimum bending radius fixed installation
5x cable Ø
Temperature range in motion
-10 to +80 °C
Temperature range for fixed installation
-40 to +80 °C
Radiation resistance
up to 80x10⁶ cJ/kg (80 Mrad)
Conductor marking
black conductors with continuous white digit marking
Conductor construction
Cu stranded wire bare, DIN VDE 0295 class 5
Screening
Tinned Cu braid, approx. 85% coverage
Outer sheath
special PVC, blue (RAL 5015)
Direct burial
Not suitable
Regulation lengths
100 m, 500 m, 1000 m
Meter marking
Oil- and chemical-resistant
Silicone- and cadmium-free
Self-extinguishing
Flame retardant
The Helukabel OZ-BL-CY is a flexible control cable with a blue outer sheath (RAL 5015), specifically designed for use in explosive atmospheres. It serves as an intrinsically safe (ignition type -i-) cable in measurement and control systems that are not earthed and have a separate circuit. The cable is manufactured in accordance with DIN VDE 0285-525-2-51 and DIN EN 50525-2-51 and is suitable for applications requiring high electromagnetic compatibility (EMC). The shielding made of tinned copper wires with a coverage of approximately 85 % ensures precise data transmission. The blue sheath colour identifies the cable as intrinsically safe according to DIN EN 60079-14 section 16.2.2 (VDE 0165 part 1). The cable is not intended for direct burial.
Applications
The OZ-BL-CY is used in industrial plants, particularly in areas with explosion hazards, where electrical energy in the form of voltage and current is limited to prevent ignition of flammable gases or dusts. The cable is suitable for flexible installation, for example in machine building, process automation, or in the petrochemical industry. The blue-marked version is clearly identified as intrinsically safe, enabling clear classification in explosion protection technology.
Functions and Equipment in Detail
The cable consists of bare copper conductors according to DIN VDE 0295 class 5, which are fine-stranded and flexible. The conductors are insulated with special PVC and marked with continuous white numerals on a black background, in accordance with DIN VDE 0293. The conductors are stranded in layers, ensuring optimal lay lengths. A separator foil is placed between the conductor layers, providing an orderly structure and mechanical stability. The shielding braid made of tinned copper wires ensures high EMC performance. The outer sheath made of special PVC is blue and features a metre marking to facilitate length measurement during installation.
Technology Explained Simply
The rated voltage is 300/500 V, meaning the cable is designed for operating voltages up to 500 V between conductor and earth and 300 V between conductors. The test voltage of 3000 V and the breakdown voltage of at least 6000 V ensure high electrical strength. The operating capacitance between conductors is approximately 140 nF/km, and between conductor and shield approximately 187 nF/km. The inductance is approximately 0.68 mH/km, and the coupling resistance is limited to a maximum of 250 Ohm/km. These values are crucial for signal quality in data and control applications. The radiation resistance up to 80 Mrad (80x10⁶ cJ/kg) makes the cable suitable for applications in radiation-exposed environments. The temperature ranges are -10 °C to +80 °C for flexible installation and -40 °C to +80 °C for fixed installation. The minimum bending radius is 10 times the cable diameter for flexible installation and 5 times for fixed installation.
Compatibility and Accessories
The cable is designed for use in intrinsically safe systems and meets the requirements of DIN EN 60079-14. Its use in un-earthed systems with a separate circuit is intended. The shielding should be contacted on both sides and over a large surface area to optimise EMC properties. The cable is not suitable for direct burial. The materials used are silicone- and cadmium-free and free from substances that interfere with paint adhesion. The PVC materials are self-extinguishing and flame-retardant according to DIN VDE 0482-332-1-2, DIN EN 60332-1-2 and IEC 60332-1-2. The cable is largely oil- and chemical-resistant.
Installation and Mounting
Installation is carried out in explosive atmospheres in accordance with the requirements of DIN EN 60079-14. The cable is flexible and can be installed either flexibly or fixed. For flexible installation, a minimum bending radius of 10 times the cable diameter must be maintained; for fixed installation, 5 times the cable diameter. The metre marking facilitates length measurement. The shielding should be contacted on both sides and over a large surface area to ensure EMC performance. The cable is not intended for direct burial.
Operational Advantages
The OZ-BL-CY offers high mechanical and electrical robustness. The flexible construction enables easy installation, even in tight bends. The shielding ensures reliable data transmission, especially in electromagnetically disturbed environments. The chemical resistance to oil and other media increases service life in industrial applications. The self-extinguishing and flame-retardant PVC materials enhance safety. The radiation resistance extends the range of applications to special environments. The clear identification via the blue sheath colour and metre marking facilitates handling and identification.
The cable is supplied in standard lengths of 100 m, 500 m and 1000 m. Technical modifications are reserved.