Further information for Helukabel H05VVC4V5-K (NYSLYCYÖ-JZ) 12G1,5 qmm (13102)
Technical data:
Special PVC control cable with oil-resistant outer sheath in accordance with DIN VDE 0285-525-2-51 / DIN EN 50525-2-51 and IEC 60227/74
Temperature range moving -5°C to +70°C fixed -40°C to +70°C
Nominal voltage U0/U 300/500 V
Test voltage core/core 2 kV, 5 minutes core/shield 2 kV, 5 minutes
Breakdown voltage min. 4000 V
Coupling resistance at 30 MHz 250 Ohm/km
Insulation resistance min. 20 MOhm x km
Minimum bending radius moving 10x cable Ø fixed 5x cable Ø
Radiation resistance up to 80x106 cJ/kg (up to 80 Mrad)
Construction:
Bare copper wire, in accordance with DIN VDE 0295 class 5, fine-stranded, BS 6360 cl.5, IEC 60228 cl.5
Core insulation made of special PVC
Core identification according to DIN VDE 0293 Black cores with continuous white numbering
Cores stranded in layers with optimal lay lengths
Inner sheath made of special PVC
Shielding braid made of tinned copper wires, coverage approx. 85%
Outer sheath made of special PVC
Sheath color gray (RAL 7001)
Properties:
The materials used in production are free from silicone and cadmium and free from substances that impair paint wetting
Tests:
PVC self-extinguishing and flame-retardant according to DIN VDE 0482-332-1-2, DIN EN 60332-1-2, IEC 60332-1
Oil-resistant according to DIN EN 60811-404
Notes:
Unshielded analogue type: H05VV5-F (NYSLYÖ-JZ)
Use:
For medium mechanical stress for flexible use with free movement without tensile stress and without forced movement in dry, damp and wet rooms, but not outdoors as a control and connection cable in machine and machine tool construction, on assembly and assembly lines, conveyor systems and production lines. Various chemical compounds cannot harm the cable either. As a damp room cable, it is also preferred for operating machines in breweries, bottling plants and washing systems. For interference-free data signal transmission in measurement, control and regulation technology, in the event that electromagnetic shielding is required. The cables may be moved after installation, provided that the cables are not mechanically overloaded during movement. These shielded cables are not designed for permanent bending stress. EMC = Electromagnetic Compatibility To optimize the EMC properties, we recommend contacting the copper braid on both sides and over a large area all around.
Standard lengths: 500 m, 1000 m
Technical changes reserved.