Further information for Helukabel 13033 hose cable H05VV5-F 25G1,0 mm² grey
General
Degree of protection
oil-resistant outer sheath made of special PVC
Operating voltage
300/500 V
Temperature range in motion
-5 °C up to +70°C
Temperature range, non-operating
-40 °C up to +70°C
Minimum bending radius moving
7,5x cable Ø
Minimum bending radius not moved
4x cable Ø
Radiation resistance
80x106 cJ/kg
Insulation resistance
20 MOhm x km
Test voltage
2 kV
Test duration
5 minutes
Dielectric strength
4000 V
Conductor marking
black conductors with continuous white digit marking
Sheath colour
Grey RAL 7001
Materials
Silicon- and cadmium-free, free of substances interfering with paint adhesion
Tests
Self-extinguishing and flame retardant according to DIN VDE 0482-332-1-2, DIN EN 60332-1-2, IEC 60332-1; oil resistant according to DIN EN 60811-404
Regulation lengths
500 m, 1000 m
Standards
DIN VDE 0285-525-2-51, DIN EN 50525-2-51, IEC 60227/75
Conductor construction
Bare Cu stranded wire, DIN VDE 0295 class 5, fine-stranded
Wire insulation
special PVC
Outer sheath
special PVC
Shielded analog type
H05VVC4V5-K (NYSLYCYÖ-JZ)
Utilization
machine and machine tool construction, conveyor and assembly lines, material handling systems, production lines, breweries, filling plants, washing plants
Operating environment
Dry, damp and wet rooms, not for outdoor use
Tensile stress
not provided
Forced motion guidance
not provided
Chemical resistance
resistant to oils and various chemical compounds
Technical changes
Reserved
Meter marking
The Helukabel cable type 13033 is a special PVC control cable with oil-resistant outer sheath, designed for flexible applications in industrial environments. It complies with standards DIN VDE 0285-525-2-51, DIN EN 50525-2-51 and IEC 60227/75 and is suitable for medium mechanical stress with free movement without tensile load. The cable is used in dry, damp and wet rooms, but not outdoors. It is particularly suitable for use in machine and tool machine construction, conveyor and assembly lines, material handling systems and production lines. Due to its chemical resistance, it is also used in breweries, filling plants and washing facilities.
Applications
The cable is designed for flexible applications where the cable may be moved after installation, provided no mechanical overload occurs. It is not intended for forced movement guidance or under tensile stress. The operating environments include dry, damp and wet rooms, with the cable not intended for outdoor use. The materials are free of silicone, cadmium and substances that could impair paint adhesion, making it particularly suitable for applications in manufacturing and machine building.
Functions and equipment in detail
The cable consists of bare Cu conductors according to DIN VDE 0295 class 5, which are fine-stranded and comply with standards BS 6360 class 5 and IEC 60228 class 5. The conductors are insulated with special PVC and marked according to DIN VDE 0293 with black conductors and continuous white digit printing. The conductors are stranded in layers with optimal lay lengths, ensuring even distribution of mechanical stress. The outer sheath is also made of special PVC and is grey in colour (RAL 7001), with an integrated meter marking to facilitate length measurement.
Technology explained simply
The rated voltage is 300/500 V, qualifying the cable for typical control and connection applications in industry. The test voltage of 2 kV over 5 minutes and the breakdown voltage of at least 4000 V ensure high electrical strength. The insulation resistance is at least 20 MOhm x km, ensuring reliable insulation even over long cable lengths. The radiation resistance up to 80x106 cJ/kg (80 Mrad) makes the cable suitable for applications in environments with increased radiation exposure. The temperature resistance is between -5°C and +70°C for moving cable, and between -40°C and +70°C for stationary cable. The minimum bending radius is 7.5 times the cable Ø for moving cable and 4 times the cable Ø for stationary cable.
Compatibility and accessories
The cable is compatible with systems requiring a control and connection cable with medium mechanical stress. As a shielded analog type, the H05VVC4V5-K (NYSLYCYÖ-JZ) is mentioned, suitable for applications with higher requirements for electromagnetic compatibility. The cable is available in standard lengths of 500 m and 1000 m, with technical changes reserved.
Installation and mounting
Installation must consider mechanical load capacity. The cable may be moved after installation, provided no mechanical overload occurs. Minimum bending radii must be observed to ensure cable lifespan. The meter marking facilitates length measurement and positioning during installation.
Operational advantages
The cable is characterised by its high chemical resistance, particularly against oils and various chemical compounds. The self-extinguishing and flame-retardant properties of the PVC sheath according to DIN VDE 0482-332-1-2, DIN EN 60332-1-2 and IEC 60332-1 increase operational safety. The oil-resistant surface ensures long service life even in dirty environments. The material release of silicone and cadmium, as well as the avoidance of paint-adhesion interfering substances, makes the cable suitable for demanding industrial applications.
Protection rating
The cable is not specified with an IP protection rating, however, the outer sheath is made of oil-resistant special PVC, ensuring high resistance against mechanical and chemical influences. Use in wet rooms is possible, but not intended for outdoor use.
Operating voltage
The rated voltage of 300/500 V is suitable for typical control and connection applications in industry. The test voltage of 2 kV over 5 minutes and the breakdown voltage of at least 4000 V ensure electrical strength.
Temperature range
The cable can be operated in the temperature range of -5°C to +70°C for moving applications and -40°C to +70°C for stationary applications.
Minimum bending radius
The minimum bending radius is 7.5 times the cable Ø for moving cable and 4 times the cable Ø for stationary cable.
Radiation resistance
The cable is radiation resistant up to 80x106 cJ/kg (80 Mrad), making it suitable for applications in environments with increased radiation exposure.
Insulation resistance
The insulation resistance is at least 20 MOhm x km, ensuring reliable insulation even over long cable lengths.
Testing
The cable meets the requirements for self-extinguishing and flame-retardant PVC according to DIN VDE 0482-332-1-2, DIN EN 60332-1-2 and IEC 60332-1. Oil resistance is tested according to DIN EN 60811-404.
Conductor identification
The conductors are marked according to DIN VDE 0293 with black conductors and continuous white digit printing, enabling clear identification.
Sheath colour
The outer sheath is grey (RAL 7001) and features a meter marking to facilitate length measurement.
Materials
The materials used are free of silicone and cadmium and free of substances that impair paint adhesion, making the cable suitable for demanding industrial applications.
Standard lengths
The cable is supplied in standard lengths of 500 m and 1000 m.