Further information for Helukabel 12861 - HELU JZ 600 HMH 12G0 75qmm Black control cable halogen free
Technical data:
halogen-free, flexible control cable, based on DIN VDE 0285-525-2-51 / DIN EN 50525-2-51 and DIN VDE 0285-525-3-11 / DIN EN 50525-3-11
Temperature range moving -15°C to +70°C fixed -40°C to +70°C
Nominal voltage U0/U 0.6/1 kV
Test voltage 4000 V
Coupling resistance max. 250 Ohm/km
Minimum bending radius moving 15x cable Ø fixed 7.5x cable Ø
Radiation resistance up to 100x106 cJ/kg (up to 100 Mrad)
Structure:
bare copper wire, according to DIN VDE 0295 cl.5, fine-wire, BS 6360 cl.5, IEC 60228 cl.5
core insulation made of halogen-free polymer
Core identification according to DIN VDE 0293 Black cores with continuous white numbering
Cores stranded in layers with optimal lay lengths
Inner jacket
Shielding braid made of tinned copper wires, coverage approx. 85%
Outer jacket made of halogen-free polymer
Jacket color: black (RAL 9005) with meter marking
Properties:
The materials used in production are silicone and cadmium-free and free from substances that impair paint wetting
Tests:
Fire test according to DIN VDE 0482-332-3-24 / BS 4066-3 / DIN EN 60332-3-24 / IEC 60332-3-24
Self-extinguishing and flame-retardant according to DIN VDE 0482-332-1-2 / DIN EN 60332-1-2 / IEC 60332-1-2
Corrosiveness of fire gases according to DIN VDE 0482-754-2 / DIN EN 60754-2 / IEC 60754-2
Halogen-free according to DIN VDE 0482-754-1 / DIN EN 60754-1 / IEC 60754-1 Smoke density according
to DIN VDE 0482-1034-1+2 / BS 7622-1+2 DIN EN 61034-1+2 / IEC 61034-1+2
Notes:
unshielded analog type: JZ-600 HMH
Use:
Halogen-free, flame-retardant control cables are used as measuring, monitoring and control cables on machine tools, assembly lines and conveyor belts, production lines, in plant engineering, in air conditioning technology, in metallurgical and steel rolling mills. For fixed installation or flexible application, with free, occasional, not constantly non-recurring movement without forced movement control and without tensile stress, with medium mechanical stress. The cable is suitable for use in dry, damp, wet rooms, outdoors (fixed installation), and on plaster. The high shielding density ensures interference-free transmission of signals and pulses. EMC = Electromagnetic Compatibility To optimize the EMC properties, we recommend contacting the copper braid on both sides and over a large area.
Standard lengths: 500 m, 1000 m
Technical changes reserved.