| General |
| Degree of protection | halogen-free - |
| Temperature range in motion | -15 °C |
| Temperature range, non-operating | -40 °C |
| Nominal voltage | 300/500 V |
| Test voltage | 2000 V |
| Minimum bending radius moving | 12.5x cable Ø - |
| Minimum bending radius not moved | 4x wire Ø - |
| Radiation resistance | 100x106 cJ/kg - |
| Wire insulation | Halogen-free polymer - |
| Conductor marking | black conductors with continuous white digit marking - |
| Outer sheath | Halogen-free polymer - |
| Sheath colour | grey (RAL 7001) - |
| Meter marking | Yes - |
| Materials | Silicon- and cadmium-free, free of substances interfering with paint adhesion - |
| Flame test | DIN VDE 0482-332-3-24, DIN EN 60332-3-24, IEC 60332-3-24 - |
| Self-extinguishing and flame retardant | DIN VDE 0482-332-1-2, DIN EN 60332-1-2, IEC 60332-1-2 - |
| Corrosivity of fire gases | DIN VDE 0482-754-2, DIN EN 60754-2, IEC 60754-2 - |
| Halogen-free | DIN VDE 0482-754-1, DIN EN 60754-1, IEC 60754-1 - |
| Smoke density | DIN VDE 0482 part 1034-1+2, DIN EN 61034-1+2, IEC 61034-1+2 - |
| Cleanroom qualified | Yes - |
| Shielded analog type | JZ-500 HMH-C - |
| Regulation lengths | 100 m, 500 m, 1000 m - |
The JZ-500 HMH from Helukabel is a halogen-free, flexible control cable manufactured in accordance with the standards DIN VDE 0285-525-2-51 / DIN EN 50525-2-51 and DIN VDE 0285-525-3-11 / DIN EN 50525-3-11. It is used as a measurement, control, and control cable in industrial applications such as machine tools, conveyor and transfer belts, production lines, plant engineering, climate technology, and in steelworks and rolling mills. The cable is suitable for fixed installation or flexible use, with occasional, non-recurring free movement without forced guidance and without tensile stress, as well as under moderate mechanical stress. It can be installed in dry, damp, and wet rooms, as well as on plaster.
Applications
This control cable is designed for use in industrial environments where high requirements are placed on material quality and fire safety. It is particularly suitable for installations operated in controlled environments, such as cleanrooms, as it is marked as cleanroom-qualified. Its use in manufacturing technology, automation technology, and process control is especially appropriate due to its mechanical and thermal resistance, as well as its halogen-free materials.
Functions and Equipment in Detail
The cable consists of bare Cu strands according to DIN VDE 0295 Class 5, which corresponds to a fine-stranded design and ensures high flexibility. The conductors are insulated with a halogen-free polymer and feature conductor identification according to DIN VDE 0293: black conductors with continuous white digit printing. The conductors are stranded in layers, ensuring optimal lay lengths to achieve even distribution of mechanical stress. The outer sheath is also made of halogen-free polymer and is gray in color (RAL 7001), with an integrated meter marking to facilitate length measurement during installation.
Technology Explained Simply
The rated voltage is 300/500 V, making the cable suitable for use in standard industrial installations. The test voltage of 2000 V ensures high electrical strength. Radiation resistance up to 100x106 cJ/kg (100 Mrad) makes the cable suitable for applications in environments with increased radiation exposure, such as in medical technology or research. The temperature resistance is between -15°C and +70°C for moving applications, and between -40°C and +70°C for non-moving applications. The minimum bending radius is 12.5 times the cable diameter for moving applications, and 4 times the cable diameter for non-moving applications.
Compatibility and Accessories
The JZ-500 HMH is offered as an unshielded variant. For applications requiring higher electromagnetic shielding, the shielded counterpart JZ-500 HMH-C is available. The cable is available in standard lengths of 100 m, 500 m, and 1000 m, with the variant described here having a length of 500 m.
Installation and Mounting
Installation is carried out by laying in fixed or flexible arrangements, ensuring that mechanical and thermal stresses remain within the specified limits. The meter marking in the outer sheath facilitates length measurement and positioning during installation. The materials are free of silicone and cadmium, as well as free of substances that interfere with paint adhesion, simplifying processing and connection to other components.
Operational Advantages
The halogen-free materials ensure low smoke emission and prevent the release of corrosive gases in the event of fire, increasing operational safety. The self-extinguishing and flame-retardant properties according to DIN VDE 0482-332-1-2 and DIN EN 60332-1-2, as well as fire testing according to DIN VDE 0482-332-3-24, guarantee high fire protection performance. The cleanroom qualification makes the cable suitable for demanding environments where contamination from material abrasion must be avoided.