Technical data:
Special PVC hose cable based on DIN VDE 0285-525-2-11 / DIN EN 50525-2-11 and IEC 60227-5
Temperature range moving -15°C to +80°C fixed -40°C to +80°C
Nominal voltage U0/U 450/750 V fixed, protected U0/U 600/1000 V
Test voltage 4000 V
Breakdown voltage min. 8000 V
Insulation resistance min. 20 MOhm x km
Minimum bending radius moving 7.5x cable Ø fixed 4x cable Ø
Radiation resistance up to 80x106 cJ/kg (up to 80 Mrad)
Structure:
Bare copper wire, in accordance with DIN VDE 0295 class 5, fine-wire, BS 6360 cl.5, IEC 60228 cl.5
Core insulation made of special PVC
Core identification according to JB/OB colour code
Cores twisted in layers with optimum lay lengths
Outer jacket made of special PVC
Jacket colour grey (RAL 7001) with meter marking
Properties:
Largely oil-resistant, oil/chemical resistance
The materials used in production are free from silicone and cadmium and free from substances that impair paint wetting
Tests:
PVC self-extinguishing and flame-retardant according to DIN VDE 0482-332-1-2, DIN EN 60332-1-2, IEC 60332-1
Notes:
'Cleanroom qualified\lashshielded analogue type: Y-CY-JB
Use:
Is used for medium mechanical stress for flexible application with free movement without tensile stress and without forced movement in dry, damp and wet rooms, but not outdoors, as a measuring, monitoring and control cable on machine tools, assembly lines and conveyor belts, Production lines, in plant engineering, in heating and air conditioning technology, in power plants, in steel and steel rolling mills.
Standard lengths: 100 m, 500 m, 1000 m.
Subject to technical changes.