Further information for Helukabel SINGLE 600-J 1G25 GN - HELU special PVC core cable 10887
Technical data:
Special PVC single core cable in accordance with UL Style 10107 and CSA AWM I/II A/B, based on DIN VDE 0285-525-2-31 / DIN EN 50525-2-31, DIN VDE 0285-525-2-51 / DIN EN 50525-2-51, in accordance with UL Std.758
Temperature range moving -5°C to +90°C fixed -40°C to +90°C
Permissible operating temperature on the conductor +90°C Nominal
voltage VDE U0/U 600/1000 V UL/CSA 600 V
Test voltage 4000 V
Breakdown voltage min. 8000 V Minimum
bending radius moving 7.5x cable Ø fixed 4x cable Ø
Radiation resistance up to 80x106 cJ/kg (up to 80 Mrad)
Structure:
Bare copper wire, finely stranded in accordance with DIN VDE 0295 cl.5, BS 6360 cl.5 or IEC 60228 cl.5
Core insulation made of special PVC in accordance with class 43, 90°C in accordance with UL Std.1581 Color: black or green-yellow
Outer jacket made of special PVC compound type TM2 in accordance with DIN VDE 0207-363-4-1/DIN EN 50363-4-1 and class 43 in accordance with UL Std.1581
Jacket color: black (RAL 9005)
with meter marking
Properties:
The materials used in production are free from silicone and cadmium and free from substances that impair paint wetting
UV-resistant
Tests PVC self-extinguishing and flame-retardant in accordance with DIN VDE 0482-332-1-2, DIN EN 60332-1-2, IEC 60332-1-2 (corresponds to DIN VDE 0472 Part 804 test type B), UL VW-1, CSA FT1
Use:
PVC single core cable suitable for medium mechanical stress for flexible use with free movement without tensile stress and without forced movement in dry, damp and wet rooms and outdoors (fixed installation). Must not be laid directly in the ground or water. This two-standard single core cable is preferably used in export-oriented mechanical engineering on machine tools, production lines and in plant construction.
Standard lengths: 100 m, 500 m, 1000 m
Subject to technical changes.