Further information for Helukabel 10711 - HELU JZ 600 4G4qmm Black Control Cable PVC
Technical data:
Special PVC control cable for locking technology based on DIN VDE 0285-525-2-51 / DIN EN 50525-2-51
Temperature range moving -15°C to +80°C fixed -40°C to +80°C
Nominal voltage U0/U 300/500 V
Test voltage 4000 V
Breakdown voltage min. 8000 V
Insulation resistance min. 20 MOhm x km
Minimum bending radius moving 7.5x cable Ø fixed 4x cable Ø
Radiation resistance up to 80x106 cJ/kg (up to 80 Mrad)
Structure:
Bare copper wire, according to DIN VDE 0295 cl.5, fine-wire, BS 6360 cl.5, IEC 60228 cl.5
Core insulation made of special PVC
Core identification according to DIN VDE 0293 orange Cores with continuous black number printing
Cores stranded in layers with optimal lay lengths
Outer jacket made of special PVC
Jacket color: orange (RAL 2003) with meter marking
Properties:
Largely oil-resistant, oil/chemical resistance
The materials used in production are silicone- and cadmium-free and free from substances that impair paint wetting
Tests:
PVC self-extinguishing and flame-retardant in accordance with DIN VDE 0482-332-1-2 / DIN EN 60332-1-2 / IEC 60332-1-2
Use:
Used for medium mechanical stress for flexible applications with free movement without tensile stress and without forced movement in dry, damp and wet rooms, but not outdoors, as a control cable in accordance with DIN EN 60204-1 or VDE 0113-1. According to the standard mentioned, it is recommended to mark insulated conductors of interlocking circuits that are fed from an external power supply and remain live when the main switch is switched off, in orange.
Standard lengths: 500 m, 1000 m
. Technical changes reserved.