| General |
| Temperature range in motion | -15 °C to +80 °C |
| Temperature range, non-operating | -40 °C to +80 °C |
| Nominal voltage | 300/500 V |
| Test voltage | 4000 V |
| Dielectric strength | min. 8000 V |
| Insulation resistance | min. 20 MΩ·km |
| Minimum bending radius moving | 7,5x Conductor Ø |
| Minimum bending radius not moved | 4x Conductor Ø |
| Conductor marking | orange conductors with continuous black digit printing |
| Wire insulation | special PVC |
| Outer sheath | special PVC |
| Sheath colour | Orange RAL 2003 |
| Copper stranded wire | bare, DIN VDE 0295 Class 5 |
| Chemical resistance | oil resistant, free of substances interfering with paint adhesion |
| Regulation lengths | 100 m, 500 m, 1000 m |
The Helukabel control cable type 10617 is a flexible special PVC cable designed specifically for use in interlock technology. It complies with the requirements of standards DIN VDE 0285-525-2-51 and DIN EN 50525-2-51 and is designed for medium mechanical stress. The cable is used in free movement without tensile stress and without forced movement guidance in dry, damp and wet indoor environments, but not outdoors. It serves as a control cable according to DIN EN 60204-1 or VDE 0113-1, where the orange marking of the conductors reflects the recommendation for interlock circuits with external power supply, which remain energized even after switching off the main switch.
Applications
The control cable 10617 is suitable for applications in industrial electrical engineering, particularly in machine and plant construction, where safe and reliable control signals must be transmitted. The use in interlock systems that remain energized during operation requires clear identification of the conductors – for this purpose, the orange color of the conductors with black digit printing is provided. The cable is designed for indoor use, including damp and wet environments, but not for outdoor use.
Functions and Equipment in Detail
The cable consists of bare copper strands according to DIN VDE 0295 class 5, ensuring a fine-stranded, flexible structure. The conductors are insulated with special PVC and stranded in layers, with optimal lay lengths ensuring even distribution of mechanical stress. The outer sheath is also made of special PVC and is colored orange (RAL 2003), with a meter marking for easy length determination. The conductor identification follows DIN VDE 0293 with continuous black digit printing on orange conductors.
Technology Explained Simply
The rated voltage is 300/500 V, indicating the maximum voltage the cable can safely transmit. The test voltage of 4000 V and the breakdown voltage of at least 8000 V ensure electrical insulation under high voltage loads. The insulation resistance of at least 20 MΩ·km ensures high electrical insulation and minimizes leakage currents. The radiation resistance up to 80 Mrad (80x10⁶ cJ/kg) makes the cable suitable for applications in environments with ionizing radiation. The temperature resistance ranges from -15 °C to +80 °C for moving applications and from -40 °C to +80 °C for non-moving applications. The minimum bending radius is 7.5 times the cable diameter for moving applications and 4 times for non-moving applications.
Compatibility and Accessories
The cable is designed for flexible applications and can be used in systems with medium mechanical stress. The materials are silicone- and cadmium-free and free from substances that interfere with paint adhesion, ensuring compatibility with painting and coating processes. The PVC insulation is self-extinguishing and flame-retardant according to DIN VDE 0482-332-1-2, DIN EN 60332-1-2 and IEC 60332-1-2, improving fire behavior characteristics.
Installation and Mounting
Installation takes place indoors, with the cable laid in free movement without tensile stress. The meter marking facilitates length measurement and positioning. The flexible structure of the strands allows easy installation, especially in tight or moving arrangements. The cable is not intended for outdoor use.
Operational Advantages
The control cable 10617 offers high mechanical and thermal load capacity, required for industrial applications. The orange marking of the conductors supports the safe identification of interlock circuits. The chemical resistance against oil and other liquids, as well as radiation resistance, expands the range of applications. The flame-retardant and self-extinguishing PVC insulation increases operational safety. The cable is available in standard lengths of 100 m, 500 m and 1000 m, simplifying planning and installation.