Further information for HAGER UF32W6N3P
Transformer and measuring panel, Univ.N, 1050x500x160mm NAR NH00, AAR Lastt125A, TAB Bayernw..0x pieces
complete transformer panel up to 100 A
, factory-preassembled and wired complete transformer panel, can be combined with other complete panels and meter cabinets, with sealable contact protection covers as standard, reinforced by means of internal gas pressure process, each with four quick-release bolts. VDE mark approval according to DIN EN 61 439 -1 and - 2 and -3 (VDE 0660 Part 600 -1 and -2 and -3), dimension standard: DIN 43 870, for installation in distribution cabinets 1100 mm high, at least 2 fields, including feed terminals up to max. 50 mm², prepared to accommodate an overvoltage protection device for busbar mounting (not included),
protection class: with cabinet door open IP3x
for installation in univers distribution cabinets 1100 mm high, at least 2 fields, at least 205 mm deep, including feed terminals up to max. 50 mm², supply line from below and discharge line upwards for direct connection,
equipped with:
1 x busbar 250 A, 5-pole, 2 fields
1 x NH00 busbar fuse base, 3-pole
1 Piece preparation for accommodating an overvoltage protection device for busbar mounting (not included)
1 piece load switch 125 A, 3-pole
1 piece N and PE terminal up to 70 mm²
1 piece measuring transformer space for accommodating the 3 VNB transformers
3 pieces circuit breakers 1-pole, 10 A B characteristic, 25 kA
1 piece 3-point meter space for accommodating the VNB transformer meter
1 piece wiring of the transformers and test terminals
1 piece test terminal according to TAB (Bayernwerk and similar)