Further information for Hager SBN116 Switch 16A 1P
General
Switching function
Off switch
Number of contacts as normally open contact
1
Number of contacts as normally closed contact
0
Number of contacts as change-over contact
0
Number of poles
1
Rated current
16 A
Rated voltage
230 V
Min. rated voltage
230 V
Rated switching capacity
0.338 kA
Short-circuit breaking capacity (Icw)
0.24 kA
Voltage type
AC
Max. lamp power
0 W
Width in number of modular spacings
1
Built-in depth
68 mm
Degree of protection (IP)
IP20
With signal lamp
The Hager SBN116 switch disconnector is a 1-pole manual disconnector for mounting in distribution systems. It is designed for the safe interruption of electrical circuits with a rated current of 16 A and a rated voltage of 230 V AC. The device is designed for use in residential and commercial buildings and features a robust construction designed for reliable operation under normal operating conditions.
Applications
This switch disconnector is intended for installation in electrical distribution boards, particularly in systems where manual disconnection of the circuit is required. It is suitable for applications in residential buildings, office buildings, and commercial facilities where safe power interruption is necessary during maintenance or in the event of a fault. The protection rating IP20 protects against contact with fingers and against solid foreign objects, but not against water or dust, so its use is exclusively intended for indoor environments.
Functions and Equipment in Detail
The SBN116 features a closing contact (1S) and no opening or changeover contacts. It is therefore designed as a pure switch disconnector, interrupting the circuit when moved to the off position. The switching function is mechanical, operated via a control element that ensures clear and unambiguous positioning. The maximum current rating is 16 A, with current ratings in categories AC21 and AC22 also being 16 A for both categories A and B.
Technology Explained Simply
The switch disconnector operates with AC (alternating current) voltage and is designed for an operating voltage of 230 V. The insulation voltage is 440 V, ensuring electrical safety under normal operating conditions. The connection terminals are screw-type and allow connection with flexible conductors in cross-sections from 1.5 to 10 mm² and rigid conductors from 1.5 to 16 mm². The mounting depth is 68 mm, the overall height is 83 mm, and the width is 17.5 mm, equivalent to 1 module width. Mounting is done on a DIN rail, with a nominal torque of 1.80 Nm specified.
Compatibility and Accessories
The switch disconnector is designed for mounting on a DIN rail and can be integrated into standard distribution boxes. Compatible accessories include the locking device MZN175, suitable for 1-pole LS-, FI-, and FI-LS switches, and the auxiliary switch ESC080 with 6 A and one closing and one opening function. These components can be used to extend functionality, for example for signaling or additional switching functions.
Mounting and Installation
Mounting is done by securing to a DIN rail in the distribution board. The connection terminals are offset, allowing for optimal placement and wiring. The connection cross-sections are defined for flexible and rigid conductors, with maximum cross-sections of 10 mm² (flexible) and 16 mm² (rigid). The operating temperature range is from -20 °C to 70 °C, and the storage and transport temperature range is from -40 °C to 80 °C. The frequency range is 50 to 60 Hz.
Operational Advantages
The SBN116 provides a clear and safe switching function with an unambiguous control element. The robust construction and use of screw-type terminals ensure a reliable connection. Compatibility with standard DIN rails and the absence of a signal lamp reduce complexity and enable easy integration into existing distribution systems. The IP20 protection rating provides sufficient protection for indoor use, with no additional protective measures required. The power loss per pole is 0.40 W, indicating low energy loss.