Further information for Hager NCN316 Circuit Breaker 3P 16A
General
Release characteristic
C
Number of poles (total)
3
Number of protected poles
3
Rated current
16 A
Rated voltage
400 V
Rated insulation voltage Ui
500 V
Rated impulse withstand voltage Uimp
6 kV
Rated short-circuit breaking capacity Icn EN 60898 at 230 V
10 kA
Rated short-circuit breaking capacity Icn EN 60898 at 400 V
10 kA
Rated short-circuit breaking capacity Icu IEC 60947-2 at 230 V
30 kA
Rated short-circuit breaking capacity Icu IEC 60947-2 at 400 V
15 kA
Voltage type
AC
Frequency
60 Hz
Current limiting class
3
Over voltage category
3
Pollution degree
2
Width in number of modular spacings
3
Built-in depth
70 mm
Degree of protection (IP)
IP20
Ambient temperature during operating
70 °C
Connectable conductor cross section multi-wired
25 mm²
Connectable conductor cross section solid-core
35 mm²
Power loss
8.27 W
Concurrently switching N-neutral
Additional equipment possible
Explosion-proof
Flush-mounted installation
Miniature circuit breaker 3-pole 10kA/15kA C-16A 3M. Miniature circuit breaker in accordance with DIN EN 60898-1 (VDE 0641-11) with time-delayed thermal release for overload protection and electromagnetic release for short-circuit protection. Suitable for the subsequent installation of additional devices. Labeling option directly on the device and individual removal from the phase busbar assembly by unlocking the quick-release top hat rail fastening.