Further information for Hager MBN325 Circuit Breaker 3P 25A
General
Release characteristic
B
Number of poles (total)
3
Number of protected poles
3
Rated current
25 A
Rated voltage
400
Rated insulation voltage Ui
500 V
Rated impulse withstand voltage Uimp
4 kV
Rated short-circuit breaking capacity Icn EN 60898 at 400 V
6 kA
Rated short-circuit breaking capacity Icu IEC 60947-2 at 400 V
10 kA
Voltage type
AC
Frequency
60
Current limiting class
3
Over voltage category
3
Pollution degree
2
Width in number of modular spacings
3
Built-in depth
70 mm
Degree of protection (IP)
IP20
Ambient temperature during operating
70
Connectable conductor cross section multi-wired
25
Connectable conductor cross section solid-core
35
Power loss
10.10 W
Concurrently switching N-neutral
Additional equipment possible
Explosion-proof
Flush-mounted installation
The Hager circuit breaker MBN325 is a 3-pole switch with a rated current of 25 A and a B characteristic, designed for the protection of electrical installations against overload and short circuit. It is suitable for use in residential and commercial buildings and is mounted in distribution boxes on three module positions. The switching capacity is 6 kA at a rated voltage of 400 V, making it suitable for typical low-voltage installations. The protection class IP20 ensures protection against contact with fingers and against solid foreign objects, but not against splashing water or dust. The operating temperature range is from -25 °C to 70 °C, with the maximum ambient temperature during operation being 70 °C.
Applications
The switch is intended for use in electrical distribution systems indoors, particularly in residential and commercial buildings. It protects wiring and consumers against excessive current loading and short circuits. The B characteristic ensures selective tripping in case of overloads, with tripping occurring at approximately 3 to 5 times the rated current. This is typical for installations with high inrush currents, such as those occurring with motors or heating appliances. The switching capacity of 6 kA at 400 V AC is sufficient for most applications in the low-voltage range.
Functions and Equipment in Detail
The MBN325 features a B tripping characteristic, enabling targeted response to overloads. The rated switching capacity Icn is 6 kA at 400 V, while the Icu according to IEC 60898-2 at 400 V is 10 kA. The rated insulation voltage Ui is 500 V, and the rated impulse voltage withstand Uimp is 4 kV. Energy limitation class 3 ensures effective limitation of thermal energy during short circuits. Pollution degree class 2 is suitable for environments with low pollution, as commonly found in residential and office buildings.
Technology Explained Simply
The switch operates with a mechanical tripping mechanism that reacts when the rated current is exceeded or in case of a short circuit. The B characteristic means that the switch trips at approximately 3 to 5 times the rated current (i.e. 75 to 125 A), which is typical for installations with high inrush currents. The switching capacity of 6 kA at 400 V AC is sufficient for most applications in the low-voltage range. The protection class IP20 protects against contact with fingers and solid foreign objects, but is not suitable for outdoor use or in damp environments. The operating temperature range of -25 °C to 70 °C allows use in a wide range of indoor spaces.
Compatibility and Accessories
The switch is compatible with various accessories that extend its functionality. These include auxiliary and signaling contacts such as MZ201 and MZ202, which can be used to transmit switching states. Phase rail models such as KDN363B, KDN363A, KDN380B, and KDN380A enable mounting in distribution boxes. Additionally, end caps (KZN023), spacers (LZ060), and sealing caps (U841) are available to optimize installation. The connection terminals are designed as screw connections and allow connection with single-core conductors up to 35 mm² and multi-core conductors up to 25 mm².
Mounting and Installation
Mounting is carried out in distribution boxes on three module positions. The installation depth is 70 mm, and the width corresponds to 3 module units. The connection terminals are designed as screw connections, with a nominal torque of 2.80 Nm for both upper and lower terminals. The terminals are designed for single-core conductors up to 35 mm² and multi-core conductors up to 25 mm². Mounting is possible in flush installations, with a clearance distance of 35 mm to be observed. The terminals are aligned, enabling easy and secure connection.
Advantages in Operation
The MBN325 provides reliable disconnection in the event of a fault and protects electrical installations against damage from overload and short circuit. The B characteristic ensures selective tripping, which limits the affected areas. The switching capacity of 6 kA at 400 V is sufficient for most applications in the low-voltage range. The power loss is 10.10 W under rated operation, indicating low energy consumption during operation. Compatibility with various accessories allows flexible adaptation to specific requirements.