Further information for Hager MBN116 Circuit Breaker 1P 16A
General
Release characteristic
B
Number of poles (total)
1
Number of protected poles
1
Rated current
16 A
Rated voltage
400
Rated insulation voltage Ui
500 V
Rated impulse withstand voltage Uimp
4 kV
Rated short-circuit breaking capacity Icn EN 60898 at 230 V
6 kA
Rated short-circuit breaking capacity Icu IEC 60947-2 at 230 V
6 kA
Voltage type
AC
Frequency
60
Current limiting class
3
Over voltage category
3
Pollution degree
2
Width in number of modular spacings
1
Built-in depth
70 mm
Degree of protection (IP)
IP20
Ambient temperature during operating
70
Connectable conductor cross section multi-wired
25
Connectable conductor cross section solid-core
35
Power loss
2.44 W
Concurrently switching N-neutral
Additional equipment possible
Explosion-proof
Flush-mounted installation
The Hager circuit breaker MBN116 is a 1-pole fuse switch for use in electrical installations. It provides protection against overload and short circuit with a rated current of 16 A and a breaking capacity of 6 kA. The B tripping characteristic ensures selective disconnection, suitable for protection functions in residential and small commercial installations. The device is designed in a 1-module format, which facilitates mounting in standard installation enclosures and minimizes space requirements.
Applications
The switch is designed for use in electrical systems with a rated voltage of 230 to 400 V AC. It is particularly suitable for use in residential buildings, small commercial enterprises, and other installations where reliable protection for individual circuits is required. The operating temperature ranges from -25 °C to 70 °C, ensuring safe operation even under variable environmental conditions. The protection class IP20 protects against contact with solid objects and prevents entry of foreign bodies, but does not protect against water or dust – therefore, the switch is intended for indoor use.
Functions and Equipment in Detail
The MBN116 features a B tripping characteristic, enabling selective disconnection in case of overload. In the event of a short circuit, the current is interrupted within 6 kA, ensuring high safety for connected wiring and devices. The rated insulation voltage is 500 V, and the rated impulse withstand voltage is 4 kV, ensuring electrical strength under transient voltage stresses. Energy limitation class 3 reduces the thermal energy released during a short circuit, contributing to the protection of the installation.
Technology Explained Simply
The switch is designed for mounting in flush-mounted installation enclosures and can be installed in any 360° mounting position. The connection terminals are designed as screw terminals, with the upper terminal equipped with a biconnect system for modular devices. This facilitates connection to other components. The connection cross-sections are 1 to 35 mm² for single-core conductors and 1 to 25 mm² for multi-core conductors. The nominal torque is 2.80 Nm for both terminals. The power loss under nominal operation is 2.44 W, indicating efficient heat dissipation.
Compatibility and Accessories
The switch is designed for use in modular installation systems and can be combined with various accessories. These include, for example, locking devices such as MZN175, cable bridges such as K67C or K67H, signal contacts such as MZ202, auxiliary contacts such as MZ201, and phase bar systems such as KDN363A, KDN363B, or KDN363F. Spacers such as LZ060 or end caps such as KZN023 can be used for heat dissipation or finishing. The use of these components enables flexible and secure integration into existing installations.
Mounting and Installation
Mounting is carried out in flush-mounted installation enclosures, with a mounting depth of 70 mm. The width corresponds to one module unit (17.5 mm), enabling compact placement in standard switchboards. The screw terminals allow for a secure and durable connection to the conductors. Installation is simple and does not require any special tools beyond the standard torque of 2.80 Nm. The 360° mounting capability offers flexibility in positioning within the enclosure.
Advantages in Operation
The MBN116 offers high reliability due to its robust construction and compliance with standards IEC 60898-1 and IEC 60947-2. The B characteristic ensures precise disconnection, protecting the function of connected devices. The low power loss of 2.44 W minimizes heat generation in the enclosure. Compatibility with various accessories enables flexible adaptation to different requirements. Compliance with the RoHS directive ensures environmentally friendly manufacturing.