Further information for HAGER NH fuse switch strip LV NH00 - LVS00100SP
General
Model
Fuse switch disconnector
Rated permanent current Iu
160 A
Max. rated operation voltage Ue AC
690 V
Conditioned rated short-circuit current Iq
100 kA
Type of electrical connection of main circuit
Screw connection
Number of poles
3
Construction size fuse insert
NH00
Release indication
None
Double interrupting
Distance between rail centre, 40 mm
Distance between rail centre, 50 mm
Distance between rail centre, 60 mm
Distance between rail centre, 100 mm
Distance between rail centre, 185 mm
NH fuse switch-disconnector LV NH00 100mm 3-pole M8.NH00 fuse switch-disconnector 160 A for busbar mounting, distance 100 mm according to DIN EN 60947-3 and IEC 60947-3, suitable for NH fuse links according to DIN 43620-1. Consists of 3-pole switch-disconnector base and sealable handle insert, touch protection on the handle, with sliding transparent window for voltage testing, all-pole switching, with universal connection screw M8.
Note: Can be mounted on the busbars using additional accessory hooks (not included in delivery).