Further information for Hager LT0050 NH000-disconnector 3x100A DIN rail
General
Number of poles
3
Rated operation current Ie
100 A
Max. rated operation voltage Ue AC
690 V
Rated insulation voltage Ui
1000 V
Construction size fuse inserts
NH000
Degree of protection (IP)
IP3X
Degree of protection (NEMA)
1
Housing depth
82 mm
Housing height
216 mm
Housing width
53 mm
Surge current capacity
1.2 kA
With error protection
Fuse switch disconnector LT NH000 top hat rail 100A, box terminal 50mm². NH000 fuse switch disconnector for mounting plate or top hat rail mounting in accordance with DIN EN 60947-3 (VDE 0660-107) and suitable for NH fuse links in accordance with DIN 43620/1. Consists of 3-pole switch base and sealable handle insert, touch protection on the handle, with sliding transparent window for voltage testing, all-pole switching, for mounting on top hat rail or mounting plate without additional cover.