Further information for Hager KDN363A Phase Bar 3P 63A
General
Number of phases
3
Number of poles
3
Suitable for number of devices
4
Pitch dimensions
17.8 mm
Cross section
10 mm²
Length
210 mm
Rated permanent current Iu
63 A
Type of electric connection
Fork
Rated surge voltage
4.5 kV
Max. rated operation voltage Ue
400 V
Colour
Grey
Width in number of modular spacings
12
Insulated
Suitable for devices with N-busbar
Suitable for devices with auxiliary switch
The Hager phase bar KDN363A is a 3-pole, modular distribution component for installation in switchgear and distribution boxes. It serves structured energy distribution and enables safe and efficient connection of multiple devices to a common power supply. The bar is rated for a nominal continuous current of 63 A and features a fork connection, allowing easy mounting and connection to cables. With a length of 210 mm and a width of 12 module units (module pitch 17.8 mm), it is compatible with standard installation systems and fits into typical distribution boxes. The color is gray, supporting visual integration into standard electrical installations.
Applications
The phase bar KDN363A is designed for use in electrical switchgear, particularly in distribution boxes where central power distribution to multiple devices is required. It is suitable for installations requiring distribution to up to four devices. Due to the maximum rated operating voltage of 400 V and the rated impulse withstand voltage of 4.5 kV, it is intended for low-voltage installations in industrial and commercial electrical applications. The bar is not designed for devices with a neutral conductor or auxiliary switches, restricting its use to pure phase distribution.
Functions and Equipment in Detail
The bar features a fork connection rated for cable cross-sections up to 10 mm². This connection ensures a secure mechanical and electrical connection suitable for continuous operation. The insulation of the terminals increases safety and prevents unintended contact. The modular design over 12 module units allows flexible adaptation to different switchgear configurations. The bar is designed for a maximum current load of 63 A, making it suitable for medium to high loads in industrial and commercial applications.
Technology Explained Simply
The nominal continuous current of 63 A means the bar can be operated continuously at this current level without causing thermal or mechanical damage. The rated operating voltage of 400 V covers typical three-phase installations in the low-voltage range. The impulse voltage withstand of 4.5 kV protects the bar against transient voltage surges, such as those caused by lightning strikes or switching operations. The fork connection design allows for quick and secure installation, with terminal insulation providing additional protection. The modular structure over 12 module units offers flexibility in positioning within distribution boxes.
Compatibility and Accessories
The phase bar KDN363A is compatible with standard installation systems and fits into distribution boxes supporting the 17.8 mm module pitch. Suitable accessories include end caps for phase bars (KZN023) and shock protection covers (KZ059). These components secure the ends of the bar and protect against unintended contact, especially in open switchgear. Combining the bar with these accessories increases safety and complements the installation.
Installation and Mounting
Installation is carried out by fitting into a suitable distribution box, where the bar can be flexibly positioned due to its modular structure over 12 module units. The fork terminals allow quick and secure connection to cables up to 10 mm². Terminal insulation reduces the risk of short circuits. The bar is intended for use in enclosed switchgear, and the use of shock protection covers is recommended to enhance safety.
Operational Advantages
The modular design and fork terminals enable quick and secure installation, reducing mounting time in switchgear. The high current rating of 63 A and the high impulse voltage withstand of 4.5 kV ensure reliable performance even under demanding conditions. Terminal insulation increases safety and reduces the risk of accidents. Compatibility with standard installation systems and the availability of suitable accessories simplify integration into existing installations.
RoHS Compliance
The phase bar KDN363A is RoHS-compliant, meaning it meets the requirements of the EU directive restricting the use of certain hazardous substances in electrical and electronic equipment. This is particularly relevant for applications in industrial and commercial environments where environmental and health standards are important.