Further information for Hager HNB201H - x250 breaker 4P 200A 40kA TM
General
Rated permanent current Iu
200 A
Rated voltage
415 V
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
40 kA
Overload release current setting
200 A
Adjustment range short-term delayed short-circuit release
0 A
Adjustment range undelayed short-circuit release
2600 A
Type of electrical connection of main circuit
Screw connection
Device construction
Built-in device fixed built-in technique
Number of auxiliary contacts as normally closed contact
0
Number of auxiliary contacts as normally open contact
0
Number of auxiliary contacts as change-over contact
0
Number of poles
4
Position of connection for main current circuit
Front side
Type of control element
Toggle
Degree of protection (IP)
IP40
Power loss
24.8 W
Integrated earth fault protection
Suitable for DIN rail (top hat rail) mounting
DIN rail (top hat rail) mounting optional
With switched-off indicator
Complete device with protection unit
Motor drive integrated
Motor drive optional
With integrated under voltage release
Circuit breaker size x250 4-pole 40kA 200A TM. Circuit breaker according to DIN EN 60947-2 size x250, with thermal (adjustable) and magnetic (adjustable) tripping to protect electrical systems and networks. Mounted on mounting plate. The three different operating states can be identified by the position of the knob (ON = top, OFF = bottom, tripped = middle position). The switches have a mechanical test button. The function of the circuit breaker can be expanded using various accessories. Including phase separators.