Further information for HAGER HHS041DC - circuit breaker h3 P160 TM 4P4D N0 100% 40A 25kA CTC
General
Rated permanent current Iu
40 A
Rated voltage
690 V
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
25 kA
Overload release current setting
40 A
Adjustment range undelayed short-circuit release
480 A
Type of electrical connection of main circuit
Screw connection
Device construction
Built-in device fixed built-in technique
Number of auxiliary contacts as normally closed contact
0
Number of auxiliary contacts as normally open contact
0
Number of auxiliary contacts as change-over contact
0
Number of poles
4
Position of connection for main current circuit
Front side
Type of control element
Toggle
Degree of protection (IP)
IP40
Power loss
27.9 W
Integrated earth fault protection
Suitable for DIN rail (top hat rail) mounting
DIN rail (top hat rail) mounting optional
With switched-off indicator
Complete device with protection unit
Motor drive integrated
Motor drive optional
With integrated under voltage release
Circuit breaker h3+ P160 TM ADJ 4P4D N0-100% 40A 25kA CTC. The molded case circuit breaker in accordance with DIN EN 60947-2 protects the electrical system and networks against overload and short circuit. The thermal release for the overload current (Ir) and the magnetic release for the instantaneous short circuit current (Ii) can be set separately. The neutral conductor protection can be activated using a controller. 0% or 100% of Ir can be set. The three different operating states can be identified by the position of the knob (ON = top, OFF = bottom, triggered = middle position). A device for locking the switching state in the ON or OFF position is integrated and can be used with a standard padlock without additional accessories. The trigger mechanism can be tested and the main contacts opened using a trigger button. A hinged cover with a captive quick-release screw provides access to the installation space for optional auxiliary contacts and other triggers. Integrated accessories can be seen and identified via a viewing window without opening the hinged cover.