General
Number of poles
4
Rated voltage
400 V
Rated current
63 A
Rated fault current
0.03 A
Rated insulation voltage Ui
400 V
Rated impulse withstand voltage Uimp
4 kV
Mounting method
DIN rail
Leakage current type
B+
Short-circuit breaking capacity (Icw)
10 kA
Surge current capacity
5 kA
Frequency
50 Hz
Degree of protection (IP)
IP20
Width in number of modular spacings
4
Built-in depth
70 mm
Ambient temperature during operating
70 °C
Pollution degree
2
Connectable conductor cross section multi-wired
16 mm²
Connectable conductor cross section solid-core
25 mm²
Power loss
9.29 W
RAL-number (akin)
7005
Voltage type
AC
Selective protection
Short-time delayed tripping
Additional equipment possible
With interlocking device
Explosion-proof
Residual current circuit breaker 4-pole 10kA 63A 30mA type B+. Universal current sensitive residual current circuit breaker (FI, RCCB) according to DIN EN 61008-1 (VDE 0664-10), DIN EN 61008-2-1 (VDE 0664-11), DIN EN 61543 (VDE 0664-30) and DIN EN 62423 (VDE 0664-40). Short-time delayed FI for protection against smooth DC and AC residual currents in the frequency range up to 100 kHz. Tripping within this frequency range up to 20 kHz occurs below 420 mA. To comply with the requirements of the installation standards DIN VDE 0100-410 and DIN VDE 0100-530. Suitable for the subsequent installation of additional equipment (installation without tools). Connection terminals with bi-connect terminals at the bottom, blue test button, residual current indicator, type Bplus. Operating indicator, top and bottom DIN rail sliders for easy installation. Labeling option directly on the device.