Further information for HAGER CDB625E - FI switch 4 pin 10kA 25A 30mA type 230/400V
General
Number of poles
4
Rated voltage
400 V
Rated current
25 A
Rated fault current
0.03 A
Rated insulation voltage Ui
400 V
Rated impulse withstand voltage Uimp
4 kV
Mounting method
DIN rail
Leakage current type
B
Short-circuit breaking capacity (Icw)
10 kA
Surge current capacity
5 kA
Frequency
50 Hz
Degree of protection (IP)
IP20
Width in number of modular spacings
4
Built-in depth
70 mm
Ambient temperature during operating
70 °C
Pollution degree
2
Connectable conductor cross section multi-wired
16 mm²
Connectable conductor cross section solid-core
25 mm²
Power loss
1.98 W
RAL-number (akin)
7005
Voltage type
AC
Selective protection
Short-time delayed tripping
Additional equipment possible
With interlocking device
Explosion-proof
Residual current circuit breaker 4-pole 10kA 25A 30mA type B. Universal current sensitive residual current circuit breaker (FI, RCCB) according to DIN EN 61008-1 (VDE 0664-10), DIN EN 61008-2-1 (VDE 0664-11), DIN EN 61543 (VDE 0664-30) and DIN EN 62423 (VDE 0664-40). Short-time delayed FI for protection against smooth DC and AC residual currents in the frequency range up to 2 kHz. To comply with the requirements of the installation standards DIN VDE 0100-410 and DIN VDE 0100-530. Suitable for the subsequent installation of additional equipment. Connection terminals with bi-connect terminals at the bottom, external blue test button, type B. Operating display, top and bottom DIN rail sliders for easy installation. Labeling option directly on the device.